APPLICATION NOTE AN‐BEI‐P2‐038 

Date: 15/02/12 

 

AN‐BEI‐P2‐038 Modbus RTU Control and Register Mapping 

 

Register 22: Pre Ramp Speed Reference Value 

This register contains the reference speed information that being used by the drive for motor speed control. The data is in Hz 
and with one decimal place (i.e. 234 = 23.4Hz) 
 

Register 23: DC bus voltage 

This register contains drive internal DC bus voltage information. The value is displayed as volts, with no decimal places. 
 

Register 24: Drive temperature 

This register contains drive temperature information. Data is in Celsius with no decimal place. 
 

 