APPLICATION NOTE AN‐BEI‐P2‐038 

Date: 15/02/12 

 

AN‐BEI‐P2‐038 Modbus RTU Control and Register Mapping 

 

Register 7: Output Frequency 

This register shows the output frequency.  
The data is 16bit integer with one decimal place. E.g. value 123 gives 12.3Hz. Value ‐234 (0xFF16) gives ‐23.4Hz. 
 

Register 8: Output Current 

This register displays the output current from the drive.  
The data is 16bit integer with one decimal place. E.g. 156 = 15.6A, 12 = 1.2A. 
 

Register 9: Output Torque 

This register displays the motor torque level.  
The data is 16bit integer with one decimal place. E.g. 1000 = 100.0% 
 

Register 10: Output Power 

This register displays the output power level.  
The data is 16bit integer with two decimal places. E.g. 1000 = 10.00kW 
 

Register 11: Digital input status 

The value in this register represents the digital status of the drive control input terminals. Bit 0 indicates the status of Input 1; Bit 
1 indicates the status of Input 2 etc...  
 

Register 12: Rating ID 

The value in this parameter includes specific drive ID information, and is not recommended to be used by customer. For more 
information regarding this parameter, please contact your local drive distributor. 
 

Register 13: Power rating 

This gives the drive power rating information to two decimal places, e.g. 075 = 0.75. The unit of this register depends on the 
drive type (KW/HP) 
 

Register 14: Supply Voltage level 

This register gives the rated input voltage for the drive.  
i.e.  

230 : 230V nominal (200 – 240 + / ‐ 10%) 

    

400: 400V nominal (380 – 480 + / ‐ 10%) 
460: 460V nominal (380 – 480 Volts + / ‐ 10%) 
 

Register 15: IO software version 

This register contains the drive IO software version info. The value includes two decimal places. 
i.e. 100 means version 1.00 
 

Register 16: Motor control processor software version 

This register contains the software version info of the motor control processor. The value includes two decimal places. E.g. 100 
means version 1.00 
 

Register 17: Drive type 

This register gives the drive internal type code. 
 

Register 20: Analog input 1 value 

This register gives the value of the analog signal applied to analog input 1 after any scaling and offsets have been applied. The 
value is a 16 bit integer where a returned value of 4096 represents the maximum input value, e.g. 100%. 
 

Register 21: Analog input 2 value 

This register gives the value of the analog signal applied to analog input 2 after any scaling and offsets have been applied. The 
value is a 16 bit integer where a returned value of 4096 represents the maximum input value, e.g. 100%. 
 