APPLICATION NOTE AN‐BEI‐P2‐038 

Date: 15/02/12 

 

AN‐BEI‐P2‐038 Modbus RTU Control and Register Mapping 

 

Memory Map: 

Table 1: Control and status registers 

Register

 

Upper byte

 

Lower Byte

 

Command

Type

Scaling

Parameter

1

 

Drive Control Command Word

 

03, 06

Read/Write

2

 

Frequency Setpoint (Reference)

03, 06

Read/Write

500 = 50.0 Hz 

3

 

Torque Setpoint (Reference)

 

03, 06

Read/Write

2000 = 200.0% 

4

 

Modbus ramp control time

 

03, 06

Read/Write

3000 = 30.00 Seconds 

5

 

Speed reference

 

03, 06

Read/Write

3000 = 50.0Hz/100Hz/200Hz 

6

 

Error code

 

Drive status

 

03

Read Only

7

 

Output Frequency

 

03

Read Only

500 = 50.0Hz 

8

 

Output Current

 

03

Read Only

100 = 10.0 Amps 

9

 

Motor Torque

 

03

Read Only

1000 = 100.0% 

P0‐12

10

 

Output Power

 

03

Read Only

1000 = 10.00kW 

11

 

Digital Input Status

 

03

Read Only

P0‐03

12

 

Rating ID

 

03

Read Only

P0‐29

13

 

Power rating

 

03

Read Only

P0‐29

14

 

Voltage rating

 

03

Read Only

P0‐29

15

 

IO Processor Software Version

 

03

Read Only

100 = 1.00 

P0‐28

16

 

Motor Control Processor Software Version

 

03

Read Only

100 = 1.00 

P0‐28

17

 

Drive Type

 

03

Read Only

P0‐29

18

 

Scope channel 1

 

03

Read Only

19

 

Scope channel 2

 

03

Read Only

20

 

Analog Input 1 Signal Level

 

03

Read Only

1000 = 100.0% 

P0‐01

21

 

Analog Input 2 Signal Level

 

03

Read Only

1000 = 100.0% 

P0‐02

22

 

Pre Ramp Speed Reference (Hz)

03

Read Only

P0‐04

23

 

DC bus Voltage

 

03

Read Only

600 = 600 Volts 

P0‐20

24

 

Drive Temperature

 

03

Read Only

40 = 40°C

P0‐21

25 

Drive Serial Number 4 

03

Read Only

P0‐30

26 

Drive Serial Number 3 

03

Read Only

P0‐30

27 

Drive Serial Number 2 

03

Read Only

P0‐30

28 

Drive Serial Number 1 

03

Read Only

P0‐30

29 

Relay Output Status 

03

Read Only

30 

kWh meter (User) 

03

Read Only

100 = 10.0kWh 

P0‐26

31 

MWh meter (User) 

03

Read Only

100 = 100MWh 

P0‐27

32 

kWh Meter 

03

Read Only

P0‐26

33 

MWh Meter 

03

Read Only

P0‐27

34 

Running time – hour 

03

Read Only

P0‐31

35 

Running time – min/sec 

03

Read Only

P0‐31

36 

Running time since last enable – hour 

03

Read Only

P0‐34

37 

Running time since last enable – min/sec 

03

Read Only

P0‐34

38 

Reserved 

39 

Room (Control PCB) temperature

03

Read Only

P0‐72

40 

Speed reference value 

03

Read Only

41 

Torque reference value 

03

Read Only

P0‐05

42 

Digital pot reference value 

03

Read Only

P0‐06

43 

P0‐80 

03

Read Only

P0‐80

44 

Reserved 

03

Read Only

45 

Reserved 

03

Read Only

 
Internal Register Access area 

Register

 

Upper byte

 

Lower Byte

 

Command

Type

Scaling

51

 

User register 1

 

03, 06

Read/Write

52

 

User register 2

 

03, 06

Read/Write

53

 

User register 3

 

03, 06

Read/Write

54

 

User register 4

 

03, 06

Read/Write

55 

User register 5 

03, 06

Read/Write

56 

User register 6 

03, 06

Read/Write

57 

User register 7 

03, 06

Read/Write

58 

User register 8 

03, 06

Read/Write

59 

User register 9 

03, 06

Read/Write

60 

User register 10 

03, 06

Read/Write

61 

User register 11 

03, 06

Read/Write

62 

User register 12 

03, 06

Read/Write