Bell & Gossett IM194R03 Grinder Pumps, Single and Three Phase, 1-1⁄4″ Discharge User Manual

Page 8

Advertising
background image

8

THREE PHASE POWER UNBALANCE

A full three phase supply consisting of three individual

transformers or one three phase transformer is recom-

mended. “Open” delta or wye connections using only

two transformers can be used, but are more likely to

cause poor performance, overload tripping or early mo-

tor failure due to current unbalance.

Check the current in each of the three motor leads and

calculate the current unbalance as explained below.

If the current unbalance is 2% or less, leave the leads as

connected.

If the current unbalance is more than 2%, current

readings should be checked on each leg using each of the

three possible hook-ups. Roll the motor leads across the

starter in the same direction to prevent motor reversal.

To calculate percent of current unbalance:

A. Add the three line amp values together.

B. Divide the sum by three, yielding average current.
C. Pick the amp value which is furthest from the average

current (either high or low).

D. Determine the difference between this amp value

(furthest from average) and the average.

E. Divide the difference by the average. Multiply the

result by 100 to determine percent of unbalance.

Current unbalance should not exceed 5% at service

factor load or 10% at rated input load. If the unbalance

cannot be corrected by rolling leads, the source of the

unbalance must be located and corrected. If, on the three

possible hookups, the leg farthest from the average stays

on the same power lead, most of the unbalance is coming

from the power source.

Contact your local power company to resolve the

imbalance.

Hookup 1

Hookup 2

Hookup 3

Starter

Terminals

L1 L2 L3

L1 L2 L3

L1 L2 L3


Motor

Leads R B W

W R B

B W R

T3 T1 T2

T2 T3 T1

T1 T2 T3

Example:

T3-R = 51 amps

T2-W = 50 amps

T1-B = 50 amps

T1-B = 46 amps

T3-R = 48 amps

T2-W = 49 amps

T2-W = 53 amps

T1-B = 52 amps

T3-R = 51 amps

Total = 150 amps

Total = 150 amps

Total = 150 amps

÷ 3 = 50 amps

÷ 3 = 50 amps

÷ 3 = 50 amps

— 46 = 4 amps

— 48 = 2 amps

— 49 = 1 amps

4 ÷ 50 = .08 or 8%

2 ÷ 50 = .04 or 4%

1 ÷ 50 = .02 or 2%

INSULATION RESISTANCE READINGS

Normal Ohm and Megohm Values between all leads and ground

Condition of Motor and Leads

Ohm Value

Megohm Value

A new motor (without drop cable).

20,000,000 (or more)

20 (or more)

A used motor which can be reinstalled in well.

10,000,000 (or more)

10 (or more)

Motor in well. Readings are for drop cable plus motor.

New motor.

2,000,000 (or more)

2 (or more)

Motor in good condition.

500,000 - 2,000,000

.5 - 2

Insulation damage, locate and repair.

Less than 500,000

Less than .5

Insulation resistance varies very little with rating. Motors of all HP, voltage and phase ratings have similar values

of insulation resistance.
Insulation resistance values above are based on readings taken with a megohmmeter with a 500V DC output.

Readings may vary using a lower voltage ohmmeter, consult factory if readings are in question.

This table was reprinted through the courtesy of Franklin Electric.

INSULATION RESISTANCE READINGS

THREE PHASE POWER UNBALANCE

Advertising