RMS Technologies R325P DRIVER User Manual

Page 18

Advertising
background image

* 0.5 MH is a typical starting point for the Common Mode Line Filters. By increasing or

decreasing the value of L you can set the drain current to a minimum to meet your

requirements.

Driver to Motor Cable AWG Table

1 Amp (Peak)

5 Amp (Peak)

Length (Feet) 10 25 50 75

100 Length (Feet) 10 25 50 75

100

Minimum

AWG

20 20 18 18

16

Minimum

AWG

16 16 14 12

12

2 Amp (Peak)

6 Amp (Peak)

Length (Feet) 10 25 50 75

100 Length (Feet) 10 25 50 75

100

Minimum

AWG

20 18 16 14

14

Minimum

AWG

14 14 14 12

12

3 Amp (Peak)

7 Amp (Peak)

Length (Feet) 10 25 50 75

100 Length (Feet) 10 25 50 75

100

Minimum

AWG

18 16 14 12

12

Minimum

AWG

12 12 12 12

12

4 Amp (Peak)

Length (Feet) 10 25 50 75

100

Minimum

AWG

18 16 14 12

12


Driver to Motor Supply Cable Wire Size

NOTE: These recommendations will provide optimal protection against EMI and RFI. The actual

cable type, wire gauge, shield type and filtering devices used are dependent on the customer’s

application and system.

NOTE: Always use Shielded/Twisted Pairs for the Driver DC Supply Cable, the AC Supply Cable

and the Driver to Motor Cable.

R325P User Manual

Page 18 of 20

5/29/2013 Version 1.01