Figure 66

Figure 67

4. The drain coupling must be connected to a
grease trap or approved container (supplied
by others).

noZZLE SECtIon

1. The nozzle section is used when the
duct is required to be equipped with a fire
suppression system or washdown is desired.

2. The nozzle section allows a spray head or
nipple to be attached to the duct through
a 1” (25) NPT coupling attached to the inner
flue and when the chimney section is in
a vertical orientation, the nozzle may be
located at the most convenient place. See

Figure 68.

3. Local authorities should always be

consulted regarding the need for fire
protection or washdown systems be installed
so that the coupling is at or above the
horizontal centerline of the chimney.

SQuarE to rounD aDaptor

1. When the hood is equipped with a square
or rectangular collar, a square to round
adaptor is needed to connect the round DIS
chimney to the hood (See Figure 69).

2. The outside dimensions of the square end
are slightly smaller than the hood collar. It
will fit inside the collar and be connected by
welding the two parts.

Figure 69

Figure 68

grEaSE tEE 90° (gt90p) / tEE 90 Dam

(t90D) (DIS onLy)
The Grease Tee 90 and the standard Tee
90 with a dam are used to provide access
for clean-out to comply with NFPA 96
requirements. They are equipped with a 1-1⁄2”
(38) high grease dam at the access port.
The access port must be closed with a tee cap

45° Tee

Tee Cap

Length

45° Elbow

Grease Dam

Drain

Grease Dam

Drain

Plain View

Horizontal

Drain

Length

Clean-Out Cap

Standard 90° Tee

Up To Fan

Hood (by others)

Drop To Hood

Nozzle

Nozzle

Not UL Listed