EFFECtIVE LEngtH
When assembling two parts together, the
joint will overlap 5/8”. So effective length is
nominal length minus 5/8”.

Effective Length

Example

Material

L36

35 3/8"

L24

23 3/8"

L18

17 3/8"

L12

11 3/8"

Table 2

Clearances

Model

B.H.A Chimney

1400°F Chimney

DIS

1"

1"

DAS

4"

4"

opEnIng tHrougH ComBuStIBLE

ConStruCtIon
The following table serves to identify the
minimum opening required when installing a
chimney through a floor, wall or roof made of
combustible material. See Table 3 and Figure 1.

Table 3

DIS Minimum Openings

Model

Roof / Floor (C)

Wall (C)

Ш5" - Ш10"

Inside Ø + 8"

Inside Ш + 8"

Ш12" - Ш36"

Inside Ø + 8"

Not Listed

Table 4

DAS Minimum Openings

Model

Roof / Floor (C)

Wall (C)

Ш5" - Ш10"

Inside Ø + 12"

Inside Ш + 12"

Ш12" - Ш36"

Inside Ø + 12"

Not Listed

WarnIng

Do not InStaLL any typE oF

InSuLatIon In tHE rEQuIrED

CLEaranCE SpaCES SurrounDIng

tHE CHImnEy.

CLEaranCES

DIS
Minimum air space clearance to combustible
construction to model DIS Chimney is 1”.
For non-combustible construction, maintain
clearances as required for installation, access
for inspection or per local code.

DaS
Minimum air space clearance to combustible
construction to DAS chimney is 4”.

See Table 2.

Chimney Outside

Diameter
Chimney Inside

Diameter
2" Insulation
Clearance Opening

Openings - Minimum

opening required when

installing a chimney through

a floor, wall or roof made of

combustible material.