5 measurement setup density and interface – WIKA DPT-10 User Manual
Page 23
+
–
min.
max.
1
2
3
4
5
+
–
Fig. 19: Measurement setup in closed vessel with superimposed steam
1
Condensate vessel
2
Blocking valve
3
Precipitator
4
Drain valve
5
DPT10
4
.5 Measurement setup density and interface
Density and interface measurement are carried out in level measure-
ment mode.
à Mount DPT10 below the lower isolating diaphragm
à The ambient temperature should be the same for both capillaries
Information:
The density measurement is only ensured at a level above the upper
measuring point. Homogeneous density allocation is a prerequisite.
=
∆p
h g
+
–
0
,3
m
Fig. 20: Measurement setup with density measurement. Density 1 and h = 0.3 m
means Δp = 29.4 mbar. With density change: e.g. measured Δp = 35.3 mbar
corresponds to density 1.2, measured Δp = 23.5 mbar corresponds to density
0
.8
Density measurement
Differential pressure transmitter DPT10 - metal measuring diaphragm • Profibus PA
23