7. The ZC20 cabinet is now ready for framing as follows:

a) Frame the ZC20 using 2”x4” studs or local building code framing. Some minor framing restrictions are

required:

1. Adjacent side walls must be at least 16” from the outer edge of the ZC20 trim panel

2. The overall opening dimensions must be at least 37 15/16” wide and 34 5/8” high.

NOTE: Maintain 1 1/2” clearance at the side walls of the cabinet and combustible material.

b) 2”x4” framing above the unit must be turned flat. This allows proper clearance from framing to chimney

(2” minimum). (See Figure 6.)

ZC20/Model 20



FIGURE 6 CHASE ENCLOSURE AND CORNER LOCATION FRAMING

Optional Fire Code
Sheet Rock And
Metal Fire Stop

Ceiling

NOTE: Follow
building and fire
codes for each
individual state.

2 In.
Min.

NBC
Radiation
Shied

15FT. MAX.

CHASE
ENCLOSE -
URE

TOPPER

STORM COLLAR

ROOF FLASHING

TRIPLE WALL PIPE

2”X 4” STUDDING

USE FIRE CODE SHEET
ROCK

NBC METAL FIRE STOP
RADIATION SHIELD

2” X 4” STUDDING

A SINGLE HEADER
MUST BE INSTALLED
ABOVE CABINET

34-5/8”

37-15/16”

17”

THESE MEASUREMENTS
ARE CRITICAL.

WARNING:

Install the hearth protector

only as specified. The hearth extension must
extend a minimum of 17” in front of the fire-
place opening and must be 37 15/16” wide
minimum.