Application data – Bryant LEGACY LINE 580J User Manual

Page 26

Advertising
background image

26

APPLICATION DATA

Min operating ambient temp (cooling):

In mechanical cooling mode, your Bryant rooftop unit can

safely operate down to an outdoor ambient temperature of

40_F (4_C) and 25_F (--4_C), with an accessory winter

start kit. It is possible to provide cooling at lower outdoor

ambient temperatures by using less outside air,

economizers, and/or accessory low ambient kits.

Max operating ambient temp (cooling):

The maximum operating ambient temperature for cooling

mode is 115_F (46_C). While cooling operation above

115_F (46_C) may be possible, it could cause either a

reduction in performance, reliability, or a protective action

by the unit’s internal safety devices.

Min mixed air temp (heating):

Using the factory settings, the minimum temperatures for

the mixed air (the combined temperature of the warm

return air and the cold outdoor air) entering the dimpled,

gas heat exchangers are:

Aluminized

Stainless Steel

50_F (10_C) continuous

45_F (7_C) intermittent

40_F (4_C) continuous

35_F (2_C) intermittent

Operating at lower mixed--air temperatures may be

possible, if a field supplied, outdoor air thermostat

initiates both heat stages when the temperature is less than

the minimum temperatures listed above. Please contact

your local Bryant representative for assistance.

Min and max airflow (heating and cooling):

To maintain safe and reliable operation of your rooftop,

operate within the heating airflow limits during heating

mode and cooling airflow limits during cooling mode.

Operating above the max may cause blow--off, undesired

airflow noise, or airflow related problems with the rooftop

unit. Operating below the min may cause problems with

coil freeze--up and unsafe heating operation. Heating and

cooling limitations differ when evaluating operating CFM,

the minimum value is the HIGHER of the cooling and

heating minimum CFM values published in Table 7 and

the maximum value is the LOWER of the cooling and

heating maximum values published in Table 7.

Heating--to--cooling changeover:

Your unit will automatically change from heating to

cooling mode when using a thermostat with an

auto--changeover feature.

Airflow:

All units are draw--through in cooling mode and

blow--through in heating mode.

Outdoor air application strategies:

Economizers reduce operating expenses and compressor

run time by providing a free source of cooling and a

means of ventilation to match application changing needs.

In fact, they should be considered for most applications.

Also, consider the various economizer control methods

and their benefits, as well as sensors required to

accomplish your application goals. Please contact your

local Bryant representative for assistance.

Motor limits, Brake horsepower (BHP):

Due to internal design of Bryant units, the air path, and

specially designed motors, the full horsepower (maximum

continuous BHP) band, as listed in Table 8 and 10, can be

used with the utmost confidence. There is no need for

extra safety factors, as Bryant motors are designed and

rigorously tested to use the entire, listed BHP range

without either nuisance tripping or premature motor

failure.

Propane heating:

Propane has different physical qualities than natural gas.

As a result, propane requires different fuel to air mixture.

To optimize the fuel/air mixture for propane, Bryant sells

different burner orifices in an easy to install accessory kit.

To select the correct burner orifices or determine the heat

capacity for a propane application, use either the selection

software, or the unit’s service manual.

High altitude heating:

High altitudes have less oxygen, which affects the fuel/air

mixture in heat exchangers. In order to maintain a proper

fuel/air mixture, heat exchangers operating in altitudes

above 2000 ft (610 m) require different orifices. To select

the correct burner orifices or determine the heat capacity

for a high altitude application, use either the selection

software, or the unit’s service manual.

High altitudes have less oxygen, which means heat

exchangers need less fuel. The new gas orifices in this

field installed kit make the necessary adjustment for high

altitude applications. They restore the optimal fuel to air

mixture and maintain healthy combustion on altitudes

above 2000 ft (610 m).
NOTE: Typical natural gas heating value ranges from
975 to 1050 Btu/ft

3

at sea level nationally. The heating

value goes down approximately 1.7% per every thousand
feet elevation. Standard factory orifices can typically be

used up to 2000 ft (610m) elevation without any
operational issues.
NOTE: For installations in Canada, the input rating
should be derated by 10% for altitudes from 2000 ft
(610m) to 4500 ft (1372m) above sea level.

580J

Advertising