Sequence of operation – Bryant LEGACY LINE 580J User Manual

Page 75

Advertising
background image

75

SEQUENCE OF OPERATION

General

The sequence below describes the sequence of operation

for an electromechanical unit with and without a factory

installed EconoMi$er IV (called “economizer” in this

sequence). For information regarding a direct digital

controller,

see

the

start--up,

operations,

and

troubleshooting manual for the applicable controller.

Electromechanical units with no economizer

Cooling —

When the thermostat calls for cooling, terminals G and Y1

are energized. As a result, the indoor fan contactor (IFC)

and the compressor contactor (C1) are energized, causing

the indoor fan motor (IFM), compressor #1, and outdoor

fan to start. If the unit has 2 stages of cooling, the

thermostat will additionally energize Y2. The Y2 signal

will energize compressor contactor #2 (C2), causing

compressor #2 to start. Regardless of the number of

stages, the outdoor fan motor runs continuously while unit

is cooling.

Heating
NOTE
: Legacy Linet (580J) units have either 1 or 2

stages of gas heat.
When the thermostat calls for heating, power is sent to W

on the Integrated Gas Controller (IGC) board. An LED

(light--emitting diode) on the IGC board turns on and

remains on during normal operation. A check is made to

ensure that the rollout switch and limit switch are closed.

If the check was successful, the induced--draft motor is

energized, and when its speed is satisfactory, as proven by

the “hall effect” sensor, the ignition activation period

begins. The burners will ignite within 5 seconds. If the

burners do not light, there is a 22--second delay before

another 5--second attempt. This sequence is repeated for

15 minutes or until the burners light. If, after the 15

minutes, the burners still have not lit, heating is locked

out. To reset the control, break 24--v power to the

thermostat.

When ignition occurs, the IGC board will continue to

monitor the condition of the rollout switch, the limit

switches, the “hall effect” sensor, as well as the flame

sensor. 45 seconds after ignition occurs, assuming the unit

is controlled through a room thermostat set for fan auto,

the indoor fan motor will energize (and the outdoor air

dampers will open to their minimum position). If, for

some reason, the over--temperature limit opens prior to the

start of the indoor fan blower, the unit will shorten the

45--second delay to 5 seconds less than the time from

initiation of heat to when the limit tripped. Gas will not be

interrupted to the burners and heating will continue. Once

the fan--on delay has been modified, it will not change

back to 45 seconds until power is reset to the control.

On units with 2 stages of heat, when additional heat is

required, W2 closes and initiates power to the second

stage of the main gas valve. When the thermostat is

satisfied, W1 and W2 open and the gas valve closes,

interrupting the flow of gas to the main burners.

If the call for W1 lasted less than 1 minute, the heating

cycle will not terminate until 1 minute after W1 became

active. If the unit is controlled through a room thermostat

set for fan auto, the indoor fan motor will continue to

operate for an additional 45 seconds then stop. If the

over--temperature limit opens after the indoor motor is

stopped, but within 10 minutes of W1 becoming inactive,

on the next cycle the time will be extended by 15 seconds.

The maximum delay is 3 minutes. Once modified, the fan

off delay will not change back to 45 seconds unless power

is reset to the control. A LED indicator is provided on the

IGC to monitor operation.

Electromechanical units with an economizer

Cooling —

When free cooling is not available, the compressors will

be controlled by the zone thermostat. When free cooling is

available, the outdoor air damper is modulated by the

EconoMi$er IV control to provide a 50_F (10_C) to 55_F

(13_C) mixed air temperature into the zone. As the mixed

air temperature fluctuates above 55_F (13_C)or below

50_F (10_C) dampers will be modulated (open or close)

to bring the mixed air temperature back within control. If

mechanical cooling is utilized with free cooling, the

outdoor air damper will maintain its current position at the

time the compressor is started. If the increase in cooling

capacity causes the mixed air temperature to drop below

45_F (7_C), then the outdoor air damper position will be

decreased to the minimum position. If the mixed air

temperature continues to fall, the outdoor air damper will

close. Control returns to normal once the mixed air

temperature rises above 48_F (9_C). The power exhaust

fans will be energized and de--energized, if installed, as

the outdoor air damper opens and closes.

If field installed accessory CO

2

sensors are connected to

the EconoMi$er IV control, a demand controlled

ventilation strategy will begin to operate. As the CO

2

level in the zone increases above the CO

2

setpoint, the

minimum position of the damper will be increased

proportionally. As the CO

2

level decreases because of the

increase in fresh air, the outdoor air damper will be

proportionally closed. For EconoMi$er IV operation, there

must be a thermostat call for the fan (G). If the unit is

occupied and the fan is on, the damper will operate at

minimum position. Otherwise, the damper will be closed.

When the EconoMi$er IV control is in the occupied mode

and a call for cooling exists (Y1 on the thermostat), the

control will first check for indoor fan operation. If the fan

is not on, then cooling will not be activated. If the fan is

on, then the control will open the EconoMi$er IV damper

to the minimum position.

580J

Advertising