FAN PERFORMANCE

Table 33 – 580J*04

1 PHASE

3 TON HORIZONTAL SUPPLY

CFM

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

Field Supplied Drive

1

Standard Static Option

Medium Static Option

900

553

0.14

681

0.22

782

0.32

870

0.42

948

0.53

975

575

0.16

700

0.25

801

0.35

888

0.46

965

0.57

1050

597

0.18

720

0.28

820

0.38

906

0.49

983

0.61

1125

620

0.21

741

0.31

839

0.42

925

0.54

1001

0.66

1200

643

0.23

762

0.34

859

0.46

944

0.58

1020

0.71

1275

667

0.27

783

0.38

879

0.50

963

0.63

1038

0.76

1350

691

0.30

805

0.42

900

0.55

983

0.68

1057

0.82

1425

715

0.34

827

0.47

920

0.60

1002

0.74

1076

0.88

1500

740

0.38

849

0.52

941

0.66

1023

0.80

1096

0.95

CFM

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2

1.4

1.6

1.8

2.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

Medium Static Option

Field Supplied Drive

2

900

1019

0.64

1084

0.76

1146

0.89

1203

1.02

1258

1.16

975

1036

0.69

1101

0.81

1162

0.94

1219

1.08

---

---

1050

1053

0.74

1118

0.86

1179

1.00

1236

1.14

---

---

1125

1071

0.79

1135

0.92

1196

1.06

1253

1.20

---

---

1200

1089

0.84

1153

0.98

1213

1.12

---

---

---

---

1275

1107

0.90

1171

1.04

1231

1.19

---

---

---

---

1350

1126

0.96

1189

1.11

---

---

---

---

---

---

1425

1144

1.03

1208

1.18

---

---

---

---

---

---

1500

1163

1.10

---

---

---

---

---

---

---

---

NOTE: For more information, see General Fan Performance Notes.

Boldface indicates field supplied drive is required.

1. Recommend using field supplied fan pulley (part no. KR11AG006) and belt (part no. KR30AE039).
2. Recommend using field supplied motor pulley (part no. KR11HY161) and belt (part no. KR30AE035).

Table 34 – 580J*04

1 PHASE

3 TON VERTICAL SUPPLY

CFM

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

0.2

0.4

0.6

0.8

1.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

Field Supplied Drive

1

Standard Static Option

Medium Static Option

900

567

0.15

688

0.22

786

0.30

871

0.37

947

0.44

975

591

0.17

710

0.26

807

0.34

891

0.42

966

0.49

1050

615

0.20

732

0.29

828

0.38

911

0.47

985

0.55

1125

641

0.23

755

0.33

849

0.42

931

0.52

1005

0.61

1200

666

0.26

778

0.37

871

0.47

952

0.57

1025

0.67

1275

693

0.29

802

0.41

893

0.53

974

0.63

1046

0.74

1350

719

0.33

826

0.46

916

0.58

995

0.70

1067

0.81

1425

746

0.38

850

0.51

939

0.64

1017

0.76

1088

0.89

1500

773

0.42

875

0.57

963

0.70

1040

0.84

1110

0.96

CFM

AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)

1.2

1.4

1.6

1.8

2.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

Medium Static Option

Field Supplied Drive

2

900

1016

0.51

1080

0.57

1139

0.64

1195

0.71

1249

0.77

975

1034

0.57

1098

0.64

1157

0.72

1213

0.79

1266

0.86

1050

1053

0.63

1116

0.71

1176

0.79

1231

0.87

1284

0.95

1125

1073

0.70

1135

0.79

1194

0.87

1250

0.96

1302

1.04

1200

1093

0.77

1155

0.87

1213

0.96

1268

1.05

1321

1.14

1275

1113

0.85

1174

0.95

1232

1.05

1287

1.15

---

---

1350

1133

0.92

1194

1.03

1252

1.14

---

---

---

---

1425

1154

1.01

1215

1.12

---

---

---

---

---

---

1500

1175

1.09

---

---

---

---

---

---

---

---

NOTE: For more information, see General Fan Performance Notes.