Heating rating table – Bryant LEGACY LINE 580J User Manual

Page 9

Advertising
background image

9

Table 4 – HEATING RATING TABLE -- NATURAL GAS & PROPANE

Units

Gas Heat

AL/SS HEAT EXCHANGER

TEMP RISE

(DEG F)

THERMAL

EFFICIENCY

(%)

AFUE

(%)

INPUT / OUTPUT

STAGE 1 (MBH)

INPUT / OUTPUT

STAGE 2 (MBH)

Sin

gle

Pha

se

04

LOW

---

72 / 59

25 --- 55

82%

81%

MED

---

115 / 93

55 --- 85

80%

80%

HIGH

---

---

---

---

---

05

LOW

---

72 / 59

25 --- 55

82%

81%

MED

---

115 / 93

35 --- 65

81%

80%

HIGH

---

150 / 120

50 --- 80

80%

80%

06

LOW

---

72 / 59

20 --- 55

82%

81%

MED

---

115 / 93

30 --- 65

81%

80%

HIGH

---

150 / 120

40 --- 80

80%

80%

Th

re

e

P

ha

se

04

LOW

---

72 / 59

25 --- 55

82%

N/A

MED

82 / 66

115 / 93

55 --- 85

80%

N/A

HIGH

---

---

---

---

---

05

LOW

---

72 / 59

25 --- 55

82%

N/A

MED

---

115 / 93

35 --- 65

81%

N/A

HIGH

120 / 96

150 / 120

50 --- 80

80%

N/A

06

LOW

---

72 / 59

20 --- 55

82%

N/A

MED

---

115 / 93

30 --- 65

81%

N/A

HIGH

120 / 96

150 / 120

40 --- 80

80%

N/A

07

LOW

---

72 / 59

15 --- 55

82%

N/A

MED

---

115 / 93

25 --- 65

81%

N/A

HIGH

120 / 96

150 / 120

35 --- 80

80%

N/A

08

LOW

---

125 / 103

20 --- 50

82%

N/A

MED

120 / 98

180 / 148

35 --- 65

82%

N/A

HIGH

180 / 147

224 / 184

45 --- 75

82%

N/A

09

LOW

---

125 / 103

20 --- 50

82%

N/A

MED

120 / 98

180 / 148

30 --- 65

82%

N/A

HIGH

180 / 147

224 / 184

40 --- 75

82%

N/A

12

LOW

120 / 98

180 / 148

25 --- 65

82%

N/A

MED

180 / 147

224 / 184

30 --- 65

82%

N/A

HIGH

200 / 160

250 / 205

35 --- 70

80%

N/A

14

LOW

120 / 98

180 / 148

20 --- 65

82%

N/A

MED

180 / 147

224 / 184

25 --- 65

82%

N/A

HIGH

200 / 160

250 / 205

25 --- 70

80%

N/A

NOTES:

Heat ratings are for natural gas heat exchangers operated at or below 2000 ft (610 m). For information on propane or alti-

tudes above 2000 ft (610 m), see the Application Data section of this book. Accessory Propane/High Altitude kits are also

available.

In the USA the input rating for altitudes above 2000 ft (610m) must be derated by 4% for each 1000 ft (305 m) above sea

level. In Canada, the input rating must be derated by 10% for altitudes of 2000 ft (610 m) to 4500 ft (1372 m) above sea level.

580J