Digital 2 point input – Rockwell Automation 1734-AENT POINT I/O EtherNet/IP Adapter Module User Manual

Page 107

Advertising
background image

Publication 1734-UM011D-EN-P - May 2011

POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 93

Digital 2 POINT Input

1734-IA2

2 POINT 120V AC Input

1734-IB2

2 POINT 10…28V DC Input, Sink

1734-IM2

2 POINT 240V AC Input

1734-IV2

2 POINT 10…28V DC Input, Source
Configuration Data

Data Type

Default

Value

Valid Data Values

Filter Off On Time - POINT 0

INT

1,000

-32,768…32,767

µs

(1)

(0…65,535)

(1)

POINT I/O Modules support the Unsigned Integer data type UINT (0…65,535 range).
RSLogix 5000 software supports the signed Integer data type INT (-32,768 …+32,767 range).
To enter Filter values from +32,768…+65,535

µs, use this conversion formula:

Desired Filter Value (in

µs) - 65536 = Entered Filter Value (in µs).

As an example, for a 40 ms filter time, 40000 - 65536 = -25536

Filter On Off Time - POINT 0

INT

1,000

-32,768…32,767

µs

(1)

(0…65,535)

Filter Off On Time - POINT 1

INT

1,000

-32,768…32,767

µs

(1)

(0…65,535)

Filter On Off Time - POINT 1

INT

1,000

-32,768…32,767

µs

(1)

(0…65,535)

Input Data

Data Type

Default

Value

Valid Data Values

Input Data - POINT 0, 1

SINT, BIT

0

0=Off

1=On

Output Data

Data Type

Default

Value

Valid Data Values

None