108 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference

1734-IT2

2 Channel Thermocouple Input, Isol.
Configuration Data

Data Type

Default

Value

Valid Data Values

Temperature Mode Channel 1

SINT

1

0=mV/Custom Scale

1=°C

2=°F

3=°K

4=°R

Cold Junction Enable Channel 1

SINT

1

0=Disabled

1=Enabled

Cold Junction Offset Channel 1

INT

0

0…7,000 (0.00…70.00)

Input Data

Data Type

Default

Value

Valid Data Values

Data Channel 0

INT

0

-32,768…32,767

Data Channel 1

INT

0

-32,768…32,767

Status Byte Channel 0

SINT

0

Bit 0 Fault

Bit 1 Calibration

Bit 2 LowAlarm

Bit 3 HighAlarm

Bit 4 LowLowAlarm

Bit 5 HighHighAlarm

Bit 6 Underrange

Bit 7 Overrange

Status Byte Channel 1

SINT

0

Bit 0 Fault

Bit 1 Calibration

Bit 2 LowAlarm

Bit 3 HighAlarm

Bit 4 LowLowAlarm

Bit 5 HighHighAlarm

Bit 6 Underrange

Bit 7 Overrange

Cold Junction Data

INT

0

-32,768…32,767

Output Data

Data Type

Default

Value

Valid Data Values

None