Rockwell Automation 1734-AENT POINT I/O EtherNet/IP Adapter Module User Manual

Page 136

Advertising
background image

Publication 1734-UM011D-EN-P - May 2011

122 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference

Program Fault Note

Programming Fault Error bit – If an incomplete, incorrect, or conflicting set
of configuration parameters is sent to the module, the Program Fault bit is
asserted and an error code placed in the Programming Error Code word
(assembly 6816). The module will not enter a normal operational state. Bit
definitions (decimal) for the error codes are:

10

An invalid assembly was chosen for poll consumption (0, 105,
or 106 are valid).

9

The decimal point position is outside of the acceptable range.

8

Counter 0 window ON & OFF values are equal and not zero; or
Counter 0 window ON & OFF value is greater than the Rollover.

7

A tie has been connected to an unprogrammed window.

6

A configuration was selected that requires the scalar and none

was programmed; or
Multiple scalars were selected.

5

The preset is out of range (Rollover).

4

A rollover of zero was programmed through PWM was not

selected;

or

A rollover was programmed and PWM was selected; or
Rollover is out of range (>0x01000000).

3

A configuration requiring a time base was selected and no gate

interval was set; or
Gate interval is out of range (>200); or
Product of time base and gate interval is greater than 3 seconds.

2

A time base was entered that is not a multiple of 10; or
Time base is out of range (>3000, or 3 seconds).

1

ZF/BF/AF were selected and no filter was programmed; or
Multiple filters were selected.

0

A reserved configuration/mode was programmed.

1734-IJ

1 Channel 5V DC Encoder / Counter

1734-IK

1 Channel 15…24V DC Encoder / Counter
Output Data

Data Type

Default

Value

Valid Data Values

Counter Control

Counter Reset

Counter Preset

Value Reset

(Stored / Accumulated Count)

SINT

BIT 0

BIT 1

BIT 2

0

0

0

0

0=Count Unchanged

1=Count Cleared

0=Count Unchanged

1=Count Set to Preset

0=Count Unchanged

1=Count Cleared