POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 121

Stored Data

To interpret values from -2,147,483,648… -1, use this conversion formula:

Stored Data Tag Value + 4,294,967,296 = Actual Stored Data Tag Value.
As an example, for a read value of -1,794,967,296:-1,794,967,296 +
4,294,967,296 = 2,500,000,000 actual value

1734-IJ

1 Channel 5V DC Encoder / Counter

1734-IK

1 Channel 15…24V DC Encoder / Counter
Input Data

Data Type

Default Value

Valid Data Values

Present Data

DINT

0

0…16,777,215

Stored Data

DINT

0

-2,147,483,648…

2,147,483,647

(0…4,294,967,295)

Status

Zero Frequency Detected

Stored Data Count_2

Stored Data Count_3

A Input Status

B Input Status

Z Input Status

Not Ready

EEPROM Fault

Program Fault

(incomplete / incorrect / conflict)

INT

BIT 1

BIT 2

BIT 3

BIT 4

BIT 5

BIT 6

BIT 13

BIT 14

BIT 15

0

0=No Fault

1=Fault Detected

Cycles through 0, 1, 2, 3, 0,

Increments after update

0=Input A/B/Z is Off

1=Input A/B/Z is On

0=Module Ready

1=Module Initializing

0=No Fault

1=EEPROM data bad

0=No Fault

1=Bad Configuration

(See Program Fault Note)