Rockwell Automation 1734-AENT POINT I/O EtherNet/IP Adapter Module User Manual

Page 110

Advertising
background image

Publication 1734-UM011D-EN-P - May 2011

96 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference

Digital 2 POINT Output –

With Over Load and Open

Load Diagnostic Status

1734-OB2E

2 POINT 10…28V DC Electronically Fused Output, Source

1734-OB2EP

2 POINT 10…28V DC Electronically Fused Protected Output, Source
Configuration Data

Data Type

Default

Value

Valid Data Values

Fault Mode - POINT 0, 1

SINT, BIT

0

0=Fault Value

1=Hold Last State

Fault Value - POINT 0, 1

SINT, BIT

0

0=Off

1=On

Program Mode - POINT 0, 1

SINT, BIT

0

0=Program Value

1=Hold Last State

Program Value - POINT 0, 1

SINT, BIT

0

0=Off

1=On

No Load Enable - POINT 0, 1

(Wire Off Diagnostic)

SINT, BIT

1

0=Disabled

1=Enabled

Auto Restart Enable - POINT 0, 1

(Over Load Behavior)

SINT, BIT

0

0=Latch Off

1=Auto Retry

Fault Latch Enable - POINT 0, 1

(Open Load or Over Load)

SINT, BIT

0

0=No Latching

1=Alarms Latch

Input Data

Data Type

Default

Value

Valid Data Values

Status Data - POINT 0, 1

(Open Load or Over Load)

SINT, BIT

0

0=Off

1=On (Load Fault)

Output Data

Data Type

Default

Value

Valid Data Values

Output Data - POINT 0, 1

SINT, BIT

0

0=Off

1=On