Rockwell Automation 1734-AENT POINT I/O EtherNet/IP Adapter Module User Manual

Page 112

Advertising
background image

Publication 1734-UM011D-EN-P - May 2011

98 POINT I/O Module and RSLogix 5000 Software Controller Tag Reference

Digital 4 POINT Output –

With Over Load and Open

Load Diagnostic Status

1734-OB4E

4 POINT 10…28V DC Electronically Fused Output, Source
Configuration Data

Data Type Default

Value

Valid Data Values

Fault Mode - POINT 0, 1, 2, 3

SINT, BIT

0

0=Fault Value

1=Hold Last State

Fault Value - POINT 0, 1, 2, 3

SINT, BIT

0

0=Off

1=On

Program Mode - POINT 0, 1, 2, 3

SINT, BIT

0

0=Program Value

1=Hold Last State

Program Value - POINT 0, 1, 2, 3

SINT, BIT

0

0=Off

1=On

No Load Enable - POINT 0, 1, 2, 3

(Wire Off Diagnostic)

SINT, BIT

1

0=Disabled

1=Enabled

Auto Restart Enable - POINT 0, 1, 2, 3

(Over Load Behavior)

SINT, BIT

0

0=Latch Off

1=Auto Retry

Fault Latch Enable - POINT 0, 1, 2, 3

(Open Load or Over Load)

SINT, BIT

0

0=No Latching

1=Alarms Latch

Input Data

Data Type Default

Value

Valid Data Values

Status Data - POINT 0, 1, 2, 3

(Open Load or Over Load)

SINT, BIT

0

0=Off

1=On (Load Fault)

Output Data

Data Type Default

Value

Valid Data Values

Output Data - POINT 0, 1, 2, 3

SINT, BIT

0

0=Off

1=On

Advertising