POINT I/O Module and RSLogix 5000 Software Controller Tag Reference 99

Digital 4 POINT Output –

With Over Load Diagnostic

Status

1734-OV4E

4 POINT 10…28V DC Electronically Fused Output, Sink
Configuration Data

Data Type Default

Value

Valid Data Values

Fault Mode - POINT 0, 1, 2, 3

SINT, BIT

0

0=Fault Value

1=Hold Last State

Fault Value - POINT 0, 1, 2, 3

SINT, BIT

0

0=Off

1=On

Program Mode - POINT 0, 1, 2, 3

SINT, BIT

0

0=Program Value

1=Hold Last State

Program Value - POINT 0, 1, 2, 3

SINT, BIT

0

0=Off

1=On

Auto Restart Enable - POINT 0, 1, 2, 3

(Over Load Behavior)

SINT, BIT

0

0=Latch Off

1=Auto Retry

Fault Latch Enable - POINT 0, 1, 2, 3

(Over Load)

SINT, BIT

0

0=No Latching

1=Alarms Latch

Input Data

Data Type Default

Value

Valid Data Values

Status Data - POINT 0, 1, 2, 3

(Over Load)

SINT, BIT

0

0=Off

1=On (Load Fault)

Output Data

Data Type Default

Value

Valid Data Values

Output Data - POINT 0, 1, 2, 3

SINT, BIT

0

0=Off

1=On