Quick Start

What This Appendix

Contains

In this quick start, you learn how to use the 1734-AENT adapter with a
ControlLogix controller for EtherNet/IP systems.

Necessary Prerequisites

Before you begin this quick start, make sure the following conditions are in
place.

• The ControlLogix controller and RSLogix software version must be

version 11 or later.

• The 1756-ENBT module must be revision 2.3 or later.
• The 1734 POINT I/O modules must be series C (except for the

1734-232ASC modules, which can be series A).

• The recommended RPIs are being used: Digital = 10 ms or higher,

Analog and Specialty = 50 ms or higher.

• The 1734-AENT POINT I/O adapter is a child to a local 1756-ENBT

module.

IMPORTANT

This quick start contains a simple set of steps and
reminders that will help you avoid errors when you are
configuring your POINT I/O system for and
EtherNet/IP network.

ATTENTION

You must use series C POINT I/O modules with the

1734-AENT adapter. Series A or B POINT I/O modules will

not work with this adapter.