Mount or replace the adapter to an existing system – Rockwell Automation 1734-AENT POINT I/O EtherNet/IP Adapter Module User Manual

Page 27

Advertising
background image

Publication 1734-UM011D-EN-P - May 2011

Install the Adapter 11

Mount or Replace

the Adapter to an

Existing System

Follow these steps to mount or replace an adapter.

1. Remove the existing adapter (if there is one) from the DIN rail as

follows:

a. Pull up on the RTB removal handle to remove the terminal block.
b. Disconnect the Ethernet connector from the adapter.
c. Remove the adjacent module from its base.
d. Use a small-bladed screwdriver to rotate the DIN-RAIL locking

screw to a vertical position.

This releases the locking mechanism.

e. Lift straight up to remove.

2. For the replacement adapter, slide the safety end cap up to remove.

This exposes the backplane and power connections.

3. Position the replacement adapter vertically above the DIN rail.

4. Make certain the DIN rail lock is in the horizontal position.

5. Slide the adapter down, allowing the interlocking side pieces to engage

the adjacent module.

6. Press firmly to seat the adapter on the DIN rail.

The adapter locking mechanism snaps into place.

7. Replace the adjacent module in its base.

8. Reconnect the Ethernet cable to the adapter.

9. Set the network address thumbwheel switches to the value used on the

replaced module. For more information, see Set the Network Address
on page 19.

10. Insert the end of the terminal block (RTB) opposite the handle into the

base unit.

This end has a curved section that engages with the wiring base.

11. Rotate the terminal block into the wiring base until it locks itself into

place.