Configure the i/o – Rockwell Automation 1734-AENT POINT I/O EtherNet/IP Adapter Module User Manual

Page 43

Advertising
background image

Publication 1734-UM011D-EN-P - May 2011

Configure the Adapter for Direct Connection in RSLogix 5000 Software 27

2. From the File menu, select New.

The New Controller dialog opens.

3. Enter an appropriate Name for the Controller, for example,

POINT_IO_Controller.

4. Select the correct Version, Chassis Type, and Slot number of the

Logix5555 controller, and the folder where you want to save the
RSLogix 5000 file (Create In). The Description is optional.

RSLogix 5000 software version 11 or later lets you choose to enable
redundancy. This example does not use redundancy. To use redundancy
in your system, check the Redundancy Enabled checkbox so that a
checkmark appears.

5. Click OK.

Configure the I/O

You now add the POINT I/O modules to the controller I/O configuration
performing these procedures.