Download the program to the controller – Rockwell Automation 1734-AENT POINT I/O EtherNet/IP Adapter Module User Manual

Page 74

Advertising
background image

Publication 1734-UM011D-EN-P - May 2011

58 Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software

The New Module Connection tab dialog opens.

8. On the Connection tab, enter 50 for the requested packet interval (RPI).

9. Keep the following unchecked:

• Inhibit Module
• Major Fault on Controller If Connection fails While in Run Mode

10. Click OK.

11. Choose File

→ Save and enter the name and location of the

RSLogix 5000 file.

Download the Program to

the Controller

Follow this procedure to download the program we just saved to the
ControlLogix controller.

1. From the main menu, choose Communications

→ Who-Active.

2. From the Who Active dialog, navigate to select the slot where the

controller is located in the chassis.