Verify the module chassis size – Rockwell Automation 1734-AENT POINT I/O EtherNet/IP Adapter Module User Manual

Page 75

Advertising
background image

Publication 1734-UM011D-EN-P - May 2011

Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software 59

3. Choose Set Project Path.

4. Choose Download.

You see the Download dialog.

5. From the Download dialog, click Download.

You see this RSLogix 5000 dialog.

6. Notice that the 1756-ENBT Bridge is now online.

If yellow triangles are present, see the following section.

Verify the Module

Chassis Size

You have now built the I/O tree in RSLogix 5000, and the RSLogix 5000
software used the chassis size from the 1734-AENT General tab. Now you
need to download this new chassis size value into the 1734-AENT adapter
hardware. This procedure synchronizes the chassis size value from the
RSLogix 5000 software into the 1734-AENT hardware. You must be online to
perform this procedure.

1. Verify that RSLogix 5000 software is online.

2. Right-click the 1734-AENT adapter under I/O Configuration in the

Project dialog.