63

Publication 1734-UM011D-EN-P - May 2011

Chapter

6

LED Status Indicators

What This Chapter Contains

Read this chapter for information about LED status indicators.

Interpret the Status Indicators

ATTENTION

You must use series C POINT I/O modules with the

1734-AENT adapter. Series A or B POINT I/O modules will

not work with this adapter.

Indication

Probable Cause

Recommended Action

Module Status
Off

No power applied to device

Apply power to the device.

Flashing

red/green

LED cycle power test (module

self-test) present.

None

Solid green

Device is operating normally.

None

Flashing red

Recoverable fault has occurred:

Firmware (NVS) update present.

Address switches changed.

Complete firmware update.

Verify address switches.

Solid red

Unrecoverable fault has occurred:

Self-test failure present

(checksum failure, or RAMtest

failure at cycle power).

Firmware fatal error present.

Replace adapter.

System Power

Field Power

43248aent

Module Status
Network Activity

Network Status

POINTBus Status