Publication 1734-UM011D-EN-P - May 2011

76 Adapter Web Pages

3. From the Diagnostic Messaging tab, click Submit to see values similar to

that in the figure.

Work with the

Configuration Pages

To work with the Configuration pages, follow these procedures, noting that
values on these pages are stored in and retrieved from non-volatile memory.

1. From the Home page, click Configuration or Expand to see the

Configuration options, if needed.

IMPORTANT

The values on these pages are in non-volatile memory.
Changes to these parameters do not take effect until you
reset or cycle power to the 1734-AENT adapter.

IMPORTANT

If you set the thumbwheels on the 1734-AENT adapter to
the value 888 and then power cycle the module, the
following occurs:

• The DHCP Enabled function is enabled (set to True).
• The Ethernet link is negotiated automatically. The Auto

Negotiate function is set to True.

• The Web server is enabled. The Disabled Web Server

function is disabled.

• The password for this page resets to the factory default.

The word password is the factory default password.

Note the value of the switches before you enter the 888
value because you return the adapter to those values once
this process is complete.