Table 5, Sensor connections -4 – CiDRA Sonar Process Monitoring System User Manual

Page 16

Advertising
background image

20909-01C Rev 04

Page 6-4

All of the following signals are energy-limited for the TB8-xx-xx-xx-03 transmitter
only. For the TB8-xx-xx-xx-04 Transmitter they are not energy-limited.

Note: These signals are not present on every model. Some models may have one-
piece screw terminal blocks and others may have two-piece pluggable terminal
blocks with either screw or spring clip terminals. These terminals will accept 0.325
to 1.31 mm

2

(22-16 AWG) conductor sizes. Conductor size 0.52 mm

2

(20AWG) or

larger cross section is recommended.

I/O NAME

OUTPUT IS LIMITED TO

LIMIT INPUT TO

Sensor 1 - HI

+12V, 48mA

Passive 4-20mA transducer

Sensor 1 - LO

-12V, 48mA

Passive 4-20mA transducer

Sensor 1 - SHD Ground

Ground shields at one end only

Sensor 2 - HI

+12V, 48mA

Passive 4-20mA transducer

Sensor 2 - LO

-12V, 48mA

Passive 4-20mA transducer

Sensor 2 - SHD Ground

Ground shields at one end only

1 – WHT

+/-8.5V, 43mA from Sensor Head

Connect only to sensor head cable

1 – BLK

+/-8.5V, 22mA from Sensor Head

Connect only to sensor head cable

2 – WHT

+/-8.5V, 43mA from Sensor Head

Connect only to sensor head cable

2 – BLK

+/-8.5V, 22mA from Sensor Head

Connect only to sensor head cable

3 – WHT

+/-8.5V, 43mA from Sensor Head

Connect only to sensor head cable

3 – BLK

+/-8.5V, 22mA from Sensor Head

Connect only to sensor head cable

4 – WHT

+/-8.5V, 43mA from Sensor Head

Connect only to sensor head cable

4 – BLK

+/-8.5V, 22mA from Sensor Head

Connect only to sensor head cable

5 – WHT

+/-8.5V, 43mA from Sensor Head

Connect only to sensor head cable

5 – BLK

+/-8.5V, 22mA from Sensor Head

Connect only to sensor head cable

6 – WHT

+/-8.5V, 43mA from Sensor Head

Connect only to sensor head cable

6 – BLK

+/-8.5V, 22mA from Sensor Head

Connect only to sensor head cable

7 – WHT

+/-8.5V, 43mA from Sensor Head

Connect only to sensor head cable

7 – BLK

+/-8.5V, 22mA from Sensor Head

Connect only to sensor head cable

8 – WHT

+/-8.5V, 43mA from Sensor Head

Connect only to sensor head cable

8 – BLK

+/-8.5V, 22mA from Sensor Head

Connect only to sensor head cable

9 – WHT

Ground

Connect only to sensor head cable

9 – BLK

Ground

Connect only to sensor head cable

10 – WHT

RS-485 bus levels

Connect only to sensor head cable

10 – BLK

RS-485 bus levels

Connect only to sensor head cable

11 – WHT

-12V nom (-14.25V max), 180mA

Connect only to sensor head cable

11 – BLK

Ground

Connect only to sensor head cable

12 – WHT

+12V nom (+14.25V max), 180mA

Connect only to sensor head cable

12 – BLK

Ground

Connect only to sensor head cable

SHD Ground

Use for drain wire of sensor head
cable

SHD Ground

Use for orange communication
wire, if present.

SHD Ground

Provisional

SHD Ground

Provisional

Table 5

Sensor Connections