SUPPLEMENTARY INSTRUCTIONS FOR SAFE
USE (NORMAL OPERATION WITH NO
OPERATOR INTERVENTION)

10.1

Keep Enclosures Closed During Use

10.1.1

Transmitter

Verify the following:

 The transmitter cover should be tightly closed and all 4 screws

installed to secure the cover.

 Cable glands should be properly installed and snug in their

mounting holes in the enclosure and snug around their cables.

 Cables shall be prevented from applying pulling or twisting

forces on the cable glands.

10.1.2

Sensor Head

Verify the following:

 All sensor head latches should be snugly mated.
 Clamps should be snugly installed on the boot seals.
 The cable connector shall be snugly latched onto the mating

connector.

 The cable shall be installed with a drip loop (if necessary) such

that water will not run along the cable toward the connector

 The cable shall be installed such that the connector will not be

subjected to twisting or pulling forces.

10.2

Periodic Inspections

Include the sonar process monitoring system in periodic inspections of
the facility.

10.2.1

Transmitter Inspections

Verify the absence of the following:

 Loose hardware or fittings
 Damage to enclosure
 Damage to seals
 Dirt or moisture inside enclosure

20909-01C Rev 04

Page 10-1