The GP16XX can be setup in one of three ways:
1. An EQP only configuration, allowing all 16 channels

to be used for LON devices.

2. One AIM mounted inside the enclosure that powers 8

individual 4-20 mA devices, with the other 8 channels

used for LON devices.

3. Two AIMs mounted inside the enclosure to power 16

individual 4-20 mA devices.

NOTE

Analog Input Modules are pre-installed with
resistors from the factory. At minimum, one channel
(for each AIM)

must remain active, otherwise a

fault will be generated.

DEFAUlT SETUP SETTINGS
If the GP16XX Gas Panel is ordered without specifying

factory settings in the Configuration Worksheet, the

following default settings will be assumed:

Range: 0-100

Low Alarm: 20

High Alarm: 40

Note: unit of measure is percent of scale.

4-20 mA DEVICE SETUP

NOTE

The following setup instruction assumes that
all wiring from the device to the AIM has been
completed and the GP16XX is powered up.
Reference the device specific instruction manual
for wiring and calibration information.

The following example is for a GT3000 gas detector

connected to a Sensor Termination Box model STB, for

use with an AIM:
1. Power up the GT3000 and allow it to reach the

normal operating mode. Refer to the GT3000

manual, 95-8616, for startup procedures.

2. From the Main screen press the SETUP button.
3. The Setup screen will open. Touch an empty channel

to open the Setup Login screen (Figure 7).

NOTE

The user ID and password will be required every
time setup is initiated from the Main screen.

4. Touch the "User ID" input field to open the User

ID Input screen (Figure 10). Using the on-screen

keyboard, type "ADMIN" then press the ENT (Enter)

button to accept the user ID.

5. The Setup Login screen will re-open. Touch the

"Password" input field to open the Password Input

screen (Figure 10). Using the on-screen keyboard,

type "DEC" and press ENT to accept the password.

6. The Setup Login screen will re-open. Press the OK

button to accept the user ID and password.

7. The Device Setup screen will open. Touch the

Custom Device ID field to activate the cursor. Type

an 8 character limit tagname for the GT3000, and

make sure to press the ENT button to submit the
tagname

.

ImpoRtANt

The tagname will not be accepted unless the ENT
button is pressed.

8. Still in the Device Setup screen, select AIM as the

device type and press the SAVE button. The Setup

screen will open, showing the activated channel.

9. Calibrate the device using information in the device

specific instruction manual.

NOTE

Calibration of 4-20 mA devices cannot be initiated
or monitored from the GP16XX, only locally on the
4-20 mA device.

Figure 10—user ID and Password Input Screen(s)

CAPS LOCK*

ESCAPE
(Return to Device
Setup Login screen)

CLEAR

(Clears the text field)

BACKSPACE

(Delete one character

at a time)

USER ID/PASSWORD

INPUT FIELD

*NOTE
IN THE USER ID AND PASSWORD INPUT SCREENS, THE CAPS LOCK IS ACTIVATED BY
DEFAULT AND MUST REMAIN ACTIVATED WHEN ENTERING THE USER ID AND PASSWORD.
BOTH THE USER ID AND PASSWORD ARE CASE SENSITIVE.