Operation – Det-Tronics GP16XX Standard Gas Panel User Manual

Page 13

Advertising
background image

1.1

95-8671

11

operation

NOTE

After configuring a device, it is highly
recommended that calibration be performed
before operation.

CAlIBRATION

ImpoRtANt

The Calibration Active and Calibration Fault
indications are only available for LON devices, and
not for 4-20 mA devices. The following instructions
are specific to LON based devices.

In regards to monitoring calibration through the GP16XX,

the general calibration procedure is as follows:

1. Initiate calibration locally at the device.
2. Activate the Point Display within the Main screen

for the device in calibration. The "Calibration

Active" indicator becomes solid white when gas is

applied (Figure 11).

3. On the Main screen, the real time gas value will

rise above zero and the applied calibration gas is

indicated when the channel contains a solid white

bar (Figure 12).

4. When calibration is successful press the BACK

button to return to the Main screen.

Calibration Fault
Calibration faults are indicated on the Point Display

when the "Calibration Fault" indicator is solid yellow

(Figure 13). On the Main screen, the channel and the

FAULT button will flash yellow (Figure 14).

Consult the device specific instruction manual for

information on how to clear faults. The indication of the

fault will remain latched on the touch screen display until

it is corrected and the RESET button is pressed.

Figure 11—Calibration active Indication on Point Display

Figure 12—Real Time Gas Value and applied Gas on Main Screen

Figure 13—Calibration Fault Indication on Point Display