Det-Tronics GP16XX Standard Gas Panel User Manual

Page 5

Advertising
background image

1.1

95-8671

3

system components

The system has three (3) main component groups – the

System Controller, LON, and 4-20 mA field devices. The

following devices are included (or optional) with the

GP16XX Gas Panel.

EQ3001 – EQP Controller (included)
The EQP Controller is the first and most critical component

of the GP16XX Gas Panel. With pre-programmed logic

from Det-Tronics' Safety System Software (S

3

), the

controller performs all communication, command, and

control functions for the system.

EQ3710AIM – Analog Input Module (optional up to 2)
The 8 channel Analog Input Module allows a device with

a calibrated 4-20 mA output signal to be connected to the

Eagle Quantum Premier Controller.

EQ2220GFM – Ground Fault Monitor (included)
The EQ2220GFM detects ground fault conditions on +/-

power and all secondary I/O circuits.

Power Supply – 24 Vdc, 10A (included)
The Power Supply provides main power to the EQP

Controller. It includes features such as voltage regulation,

high efficiency, and high power factor.

Pro-face Human Interface Machine (HMI) – (included)
The HMI touch screen consists of several graphical

screens that permit the setup, operation, and

interrogation of the connected field devices. See the

Operator Interface section for detailed descriptions of

the HMI touch screen.

FIElD DEVICES
The following field devices are GP16XX compatible:

PIRECl – PointWatch Eclipse

®

The PointWatch Eclipse Model PIRECL is a diffusion-

based, point-type infrared gas detector that provides

continuous monitoring of combustible hydrocarbon gas

concentrations in the range of 0 to 100% LFL. When

used with the GP16XX, the PIRECL can be setup through

the AIM or LON, depending on the model type.

UD10-DCU – FlexVu Universal Display

The FlexVu Model UD10-DCU is designed for applications

that require a gas detector with digital readout of detected

gas levels. Its LON interface board makes the UD10-

DCU compatible with Eagle Quantum Premier systems

by digitizing the 4-20 mA analog signal from the attached

sensor/transmitter. The digitized value is then transmitted

as a process variable over the LON to the EQP controller.

The UD10-DCU can be used with various 4-20 mA gas

detection devices (with or without HART), including the

following Det-Tronics field devices:
• GT3000

• PIRECL

• PIR9400

• OPECL

• CGS

• NTMOS.

EQ22xxDCU/DCUEX – Digital Communication Unit
The EQ22xx series of digital communication units for

catalytic, combustible and toxic gas sensors digitizes the

analog signal and transmits the value to the controller.

4-20 mA Devices
Connect 4-20 mA devices to the GP16XX via:
• AIM

• UD10-DCU

• EQ22xxDCU/DCUEX.

Reference Table 1 for the documentation list that contains

device specific information on approvals, installation,

calibration, and maintenance.

TITlE

FORM NUMBER

EQP Controller

95-8533

AIM

95-8533/90-1183

EQ22xxDCU

95-8533/90-1118

UD10-DCU

95-8656

ECLIPSE

95-8526

Table 1—EQP Device Specific Documentation