operator interFace

The HMI touch screen is located on the front of the

enclosure door, and consists of several graphical

screens that permit the setup, operation, and

interrogation of the connected field devices. These

screens include the Main screen, Setup screen, Device

Setup screen, and Event Log screen.

MAIN SCREEN
The Main screen displays the overall status of the devices

within the GP16XX gas panel. The vertical gauges

represent the 16 available channels (Figure 4), and each

channel can inherit any of the following characteristics:

Solid Blue Channel

—Channel not active.

Solid Black Channel

—Device active with zero gas.

Solid White Channel

—Gas is present below alarm

setpoint.

Solid yellow Channel

—System fault detected.

Flashing Red Channel

—Gas is present above low alarm

setpoint.

Solid Red Channel

—Gas is present above high alarm

setpoint.

A Logic Defined tagname and a Custom Device ID

tagname will appear above a channel after setup has

been completed for that channel.

Note

the Logic Defined tagname, beginning with
"GD–", cannot be altered. It is a tagname that
references each channel as a "Gas Detector"
and is used for identifying devices in the event
logs. Custom Device IDs are entered in the
setup screen.

Figure 3—LON Wiring Terminal

CUSTOM

DEVCE ID

REAL TIME

GAS VALUE

ACTIVE

CHANNEL

LOGIC DEFINED

TAGNAME

EMPTY

CHANNEL

Figure 4—Main Screen