Wiring – Det-Tronics UD20 FlexVu Explosion-Proof Universal Display Unit User Manual

Page 6

Advertising
background image

3.1

95-8620

4

DEvICE mOUNTINg ORIENTATION
The gas detector must be mounted in a vertical position

only, with the sensor pointing down. See Figure 2.

Important

The GT3000 must be oriented with the LEDs
facing forward so they are easily visible to
personnel within the area. To ensure correct
orientation (the LEDs are not visible when power
is off), position the GND lug on the left hand side
and the calibration notch to the front. Note that the
LEDs are located directly above the calibration
notch.

SENSOR SEpARATION
Det-Tronics sensor termination boxes (Model STBs)

enable the installation of the GT3000 separately from

the UD20 Universal Display Unit. Two-conductor

shielded cable is required to prevent possible nuisance

EMI/RFI.

The maximum cable length between the termination

box and the UD20 is 2000 ft.

WirinG

pOwER SUpply REqUIREmENTS
Calculate the total gas detection system power

consumption rate in watts from cold start-up. Select a

power supply with adequate capability for the calculated

load. Ensure that the selected power supply provides

regulated and filtered 24 Vdc output power for the

entire system. If a back-up power system is required,

a float-type battery charging system is recommended.

If an existing source of 24 Vdc power is being utilized,

verify that system requirements are met.

NOTE

The UD20 and GT3000 communicate using
HART protocol, which requires a power supply
with low noise levels for proper operation. (For
detailed information regarding power supply
specifications, refer to the HART Communication
Foundation’s document “FSK Physical Layer
Specification” HCF_SPEC-54.)

wIRINg CAblE REqUIREmENTS
Always use proper cabling type and diameter for input

power as well as output signal wiring. 22 to 14 AWG

shielded stranded copper wire is recommended.

Always install a properly sized, master power fuse or

breaker on the system power circuit.

NOTE

The use of shielded cable in conduit or shielded
armored cable is required. In applications where
the wiring is installed in conduit, dedicated
conduit is recommended. Avoid low frequency,
high voltage, and non-signaling conductors to
prevent nuisance EMI problems.

CaUtIon

The use of proper conduit installation techniques,
breathers, glands, and seals is required to prevent
water ingress and/or maintain the explosion-proof
rating.

wIRINg pROCEDURE
Refer to Figures 3 and 4 for wiring illustrations.

GREEN LED

CALIBRATION NOTCH

B2436

GND LUG

Figure 2—Correct Mounting Orientation