3.1

95-8620

5

+

24 VDC

UD20 DISPLAY UNIT

B2406

J2-6

J2-5

J2-4

J2-3

J2-2

J2-1

J2

NOTE 1 CONNECT THE GREEN SENSOR LEAD TO THE CHASSIS GROUND LUG

ON THE INSIDE BOTTOM OF THE UD20 DISPLAY UNIT ENCLOSURE.

NOTE 2 250 OHM RESISTOR REQUIRED (INCLUDED).

NOTE 3 EXTERNAL HART COMMUNICATION DEVICES CAN BE CONNECTED ACROSS

THE 250 OHM RESISTOR, ACROSS J2-5 AND J2-6, OR ACROSS J2-2 AND J2-3.

NOTE 4 JUNCTION BOX MUST BE ELECTRICALLY CONNECTED TO EARTH GROUND.

NOTE 5 GROUND THE SHIELD AT THE POWER SOURCE END ONLY.

SEE NOTES 2 AND 3

SEE NOTE 5

GT3000

GAS DETECTOR

+

+

SHIELD

SHIELD

SENSOR

LOOP

POWER

LOOP

BLACK

RED

GREEN

SEE NOTE 1

HAZARDOUS LOCATION

NON-HAZARDOUS LOCATION

Figure 3—Basic Wiring for Explosion Proof UD20 with GT3000

+

24 VDC

UD20 DISPLAY UNIT

B2483

J2-6

J2-5

J2-4

J2-3

J2-2

J2-1

J2

NOTE 1 GROUND THE SHIELD AT THE POWER SOURCE END ONLY.

NOTE 2 250 OHM RESISTOR REQUIRED (INCLUDED).

NOTE 3 EXTERNAL HART COMMUNICATION DEVICES CAN BE CONNECTED ACROSS

THE 250 OHM RESISTOR, ACROSS J2-5 AND J2-6, OR ACROSS J2-2 AND J2-3.

NOTE 4 JUNCTION BOXES MUST BE ELECTRICALLY CONNECTED TO EARTH GROUND.

BLACK

RED

SEE NOTE 1

SEE NOTES 2 AND 3

SEE NOTE 1

GT3000

GAS DETECTOR

SENSOR TERMINATION BOX

RED

RED

BLA

CK

BLACK

GREEN

+

+

SHIELD

SHIELD

SENSOR

LOOP

POWER

LOOP

HAZARDOUS LOCATION

NON-HAZARDOUS LOCATION

Figure 4—Basic Wiring for Explosion Proof UD20 and GT3000 with Terminal Box

Advertising