3.1

95-8620

7

CAlIbRATION pROCEDURE
1. Clean air must be present at the sensor prior

to initiating calibration. The use of bottled air is

recommended.

2. Calibration can be initiated in one of two ways:

A. Hold the calibration magnet against the

designated location on the sensor module (see

Figure 5) until the green LED turns off and the

yellow LED turns on steady (approximately one

second).

B. Initiate calibration via the magnetic switches on

the UD20. Select Main Menu > Device Cal >

Calibration > Execute.

The UD20 indicates “Waiting for Zero”. The

transmitter immediately begins taking zero readings.

3. When the zero calibration is complete, the yellow

LED changes from steady to blinking and the UD20

indicates “Waiting for Gas”. Apply the calibration

gas to the sensor. When gas is detected, the UD20

indicates “Waiting for Span”.

4. When the yellow LED turns off and the UD20

indicates “Remove Cal Gas”, remove the calibration

gas. The gas level at the sensor gradually returns to

zero. The green LED turns on steady to indicate that

the device has returned to normal operation, using

the new calibration data.

INpUT TRIm
The input current loop of the UD20 is trimmed at the

factory. However, it can also be trimmed in the field

using the following automated process.

Navigate through the menu to “Input Loop Cal”.

Main Menu
Process Vars
Display Status
Device Status
Device Setup
Device Cal
Device Test

Device Setup

HART Option
RTC
Write Protect
Input Loop Cal
Contrast Control

Upon entering Input Loop Cal, the UD20 commands

the detector to output 4 mA, and then automatically

calibrates its own input. The UD20 then commands the

detector to output 20 mA, and subsequently calibrates

its own input.

specificAtions

UD20 UNIvERSAl DISplAy UNIT

OPERATiNG VOLTAGE—

24 Vdc nominal, operating range is 19 to 30 Vdc.

UD20 maximum loop voltage drop (Vd) 5.0 volts.

Maximum loop supply 30.0 Vdc.

OPERATiNG POWER—

0.8 watt maximum.

OPERATiNG CURRENT—

A minimum of 3.5 mA.

CURRENT OUTPUT—

Linear 4-20 mA

(with HART output directly from GT3000).

250 ohm termination resistor is required (included).

OPERATiNG TEMPERATURE—

–20°C to +70°C.

STORAGE TEMPERATURE—

–40°C to +70°C.

HUMiDiTy RANGE—

5 to 95% RH (Det-Tronics verified).

SENSOR COMPATiBiLiTy—

The UD20 can be used with any of the Det-Tronics

GT3000 line of gas detectors.

LED

PLACE MAGNET HERE

TO ACTIVATE INTERNAL

MAGNETIC SWITCH

A2452

Figure 5—Location of Magnetic Switch on GT3000 Detector