9

9.1

95-8616

+

24 VDC

A2502

NOTE 1 GROUND THE SHIELD AT THE POWER SOURCE

END ONLY.

NOTE 2 250 OHM RESISTOR REQUIRED FOR HART

MENU ACCESS.

NOTE 3 EXTERNAL HART COMMUNICATION DEVICES

CAN BE CONNECTED ACROSS THE 250 OHM

RESISTOR OR ACROSS THE GT3000.

NOTE 4 JUNCTION BOX MUST BE ELECTRICALLY

CONNECTED TO EARTH GROUND.

BLACK

RED

SEE NOTES 2 & 3

SEE NOTE 1

GT3000

GAS DETECTOR

SENSOR TERMINATION BOX

RED

RED

BLA

CK

BLACK

GREEN

Figure 7—GT3000 Wired to Sensor Termination Box in Stand-Alone Configuration (Explosion-Proof)

+

24 VDC

A2530

NOTE 1 GROUND THE SHIELD AT THE POWER SOURCE

END ONLY.

NOTE 2 250 OHM RESISTOR REQUIRED FOR HART

MENU ACCESS.

NOTE 3 EXTERNAL HART COMMUNICATION DEVICES

CAN BE CONNECTED ACROSS THE 250 OHM

RESISTOR OR ACROSS THE GT3000.

NOTE 4 JUNCTION BOX MUST BE ELECTRICALLY

CONNECTED TO EARTH GROUND.

BLACK

RED

SEE NOTES 2 & 3

SEE NOTE 1

GT3000

GAS DETECTOR

SENSOR TERMINATION BOX

RED

RED

BLA

CK

BLACK

GREEN

HAZARDOUS LOCATION

NON-HAZARDOUS LOCATION

INTRINSIC

S

AFETY

B

ARRIER

Figure 8— GT3000 Wired to Sensor Termination Box in Stand-Alone Configuration (Intrinsically Safe)