Det-Tronics GTS Sensor Module User Manual

Page 13

Advertising
background image

11

9.1

95-8616

Figure 11—GT3000 Wired Directly to the UD10 Display Unit / UD10 Wired to PLC with 4-20 mA Non-Isolated Sourcing Output

GT3000

GAS DETECTOR

BLACK

RED

GREEN

SEE NOTE 1

NOTE 1

CONNECT THE GREEN DETECTOR LEAD

TO THE CHASSIS GROUND LUG ON THE

INSIDE BOTTOM OF THE DISPLAY UNIT

ENCLOSURE.

NOTE 2

JUNCTION BOXES MUST BE ELECTRICALLY

CONNECTED TO EARTH GROUND.

C2453

NON-HAZARDOUS LOCATION

HAZARDOUS LOCATION

Sensor Connector

Power Supply Connector

Output Loop

Connector

MODBUS

Connector

R

ela

y Connect

or

P1

J2

J3

J4

P2

4-20 mA +

4-20 mA –

SHIELD

COM

RS485 A

RS485 B

HIGH ALARM COM

HIGH ALARM NC

HIGH ALARM NO

AUX ALARM COM

AUX ALARM NC

AUX ALARM NO

LOW ALARM COM

LOW ALARM NC

LOW ALARM NO

FAULT COM

FAULT NC

FAULT NO

24 VDC

24 VDC

+

SHIELD

24 VDC

24 VDC

+

SHIELD

SHIELD

C

ALIBR

A

TE

24 VDC

4-20 mA

24 VDC

+

P1-3

P1-2

P1-1

J2-3

J2-2

J2-1

J4-1

J4-2

J4-3

J4-4

J4-5

J4-6

J4-7

J4-8

J4-9

J4-10

J4-11

J4-12

J3-1

J3-2

J3-3

J3-4

J3-5

P2-6

P2-5

P2-4

P2-3

P2-2

P2-1

UD10

DISPLAY UNIT

24 VDC

INPUT

4-20 mA

PLC 4-20 mA INPUT CARD

+

250

OHMS

MINIMUM

Notes: Resistor may be external if voltage input card is used.

Sinking resistance at PLC must be 250 ohms minimum

for HART communication.

P12

Figure 12—GT3000 Wired Directly to the UD10 Display Unit / UD10 Wired to PLC with 4-20 mA Isolated Sourcing Output

GT3000

GAS DETECTOR

BLACK

RED

GREEN

SEE NOTE 1

NOTE 1

CONNECT THE GREEN DETECTOR

LEAD TO THE CHASSIS GROUND

LUG ON THE INSIDE BOTTOM OF

THE DISPLAY UNIT ENCLOSURE.

NOTE 2

JUNCTION BOXES MUST BE

ELECTRICALLY CONNECTED

TO EARTH GROUND.

C2479

NON-HAZARDOUS LOCATION

HAZARDOUS LOCATION

Sensor Connector

Power Supply Connector

Output Loop

Connector

MODBUS

Connector

R

ela

y Connect

or

P1

J2

J3

J4

P2

4-20 mA +

4-20 mA –

SHIELD

COM

RS485 A

RS485 B

HIGH ALARM COM

HIGH ALARM NC

HIGH ALARM NO

AUX ALARM COM

AUX ALARM NC

AUX ALARM NO

LOW ALARM COM

LOW ALARM NC

LOW ALARM NO

FAULT COM

FAULT NC

FAULT NO

24 VDC

24 VDC

+

SHIELD

24 VDC

24 VDC

+

SHIELD

SHIELD

C

ALIBR

A

TE

24 VDC

4-20 mA

24 VDC

+

P1-3

P1-2

P1-1

J2-3

J2-2

J2-1

J4-1

J4-2

J4-3

J4-4

J4-5

J4-6

J4-7

J4-8

J4-9

J4-10

J4-11

J4-12

J3-1

J3-2

J3-3

J3-4

J3-5

P2-6

P2-5

P2-4

P2-3

P2-2

P2-1

UD10

DISPLAY UNIT

24 VDC

24 VDC

INPUT

4-20 mA

PLC 4-20 mA INPUT CARD

+

+

250

OHMS

MINIMUM

Notes: Resistor may be external if voltage input card is used.

Sinking resistance at PLC must be 250 ohms minimum

for HART communication.

P12

Advertising