Replacement parts, Device repair and return – Det-Tronics PIRVOLHV Volumetric Infrared Hydrocarbon Gas Process Monitor for Heavy Hydrocarbons User Manual

Page 13

Advertising
background image

11

3 .1

95-8632

REPLACEMENT PARTS

The PIRVOLHV is not designed to be repaired in the field.

If a problem should develop, refer to the Troubleshooting

section. If it is determined that the problem is caused by

an electronic defect, the device must be returned to the

factory for repair.

DEVICE REPAIR AND RETURN

Prior to returning devices, contact the nearest local

Detector Electronics office so that a Return Material

Identification (RMI) number can be assigned. a

written statement describing the malfunction must
accompany the returned device or component to
assist and expedite finding the root cause of the
failure.

Pack the unit properly. Always use sufficient packing

material. Where applicable, use an antistatic bag as

protection from electrostatic discharge.

NOTE

Det-Tronics reserves the right to apply a service
charge for repairing returned product damaged as
a result of improper packaging.

Return all equipment transportation prepaid to the factory

in Minneapolis.

NOTE

It is highly recommended that a complete spare
be kept on hand for field replacement to ensure
continuous protection.

Table 3—Calibration Sequence

Description

Current

LED

Operator action

Normal operation/no gas present

4.0 mA

Off

If the possibility of background gases exists,

purge the sensor with clean air to ensure accurate

calibration.

Initiate calibration

2.2 mA

On steady

Initiate the calibration sequence by holding the

calibration magnet against the side of the termination

box or activating the external calibrate pushbutton for

one second.

Zero calibration complete

2.0 mA

Flashing

Re-apply magnet (or activate switch) for one second.

Span calibration is not required. Device will revert to

live operation using new zero level and original span

level from factory calibration.

Calibration fault indication

1.6 mA

Off

See Troubleshooting Table.

NOTE: Failure to re-apply magnet to set zero level will result in Fault status if span gas is not applied. Span gas is typically

applied at the factory only.

Advertising