3 .1

95-8632

CURRENT OUTPUT—

4 to 20 mA current source (non-isolated). For output

levels below 4.0 mA, refer to Table 1.

To convert PIRVOLHV current output to % by volume gas

concentration, use the following formula:

(milliamp signal – 4.0) x 6.25 = % by volume propane

Example:

(4.0 – 4.0) x 6.25 = 0%

(12.0 – 4.0) x 6.25 = 50% by volume

(20.0 – 4.0) x 6.25 = 100% by volume.

Maximum loop resistance: 580 ohms at +24 Vdc. See

Figure 1 for further information.

WIRING—

The PIRVOLHV has five 22 AWG wires, 20 inches (50 cm)

long.

Red = + 24 volts dc

Black = – (common)

White = 4 to 20 mA signal output

Yellow = Calibration input

Green = Chassis ground

Field Wiring: 18 AWG minimum is recommended for field

wiring. Larger diameter wire may be required to maintain

a minimum of 18 Vdc (including ripple) at the sensor for all

operating conditions (see Figure 2). For maximum EMI/

RFI protection, shielded cable is recommended.

TEMPERATURE RANGE—

Operating: –40°F to +167°F (–40°C to +75°C).

Storage:

–40°F to +185°F (–40°C to +85°C).

HUMIDITY (non-condensing)—

0 to 99% relative humidity (Det-Tronics verified)

5 to 95% relative humidity (CSA verified).

ENCLOSURE MATERIALS—

Copper-free aluminum (clear anodized) or 316 stainless

steel.

SAMPLE DRAW CUP—

Material:

Aluminum or stainless steel.

Fittings:

Nickel-plated Brass.

Tubing Size: 1/4 inch O.D.

DIMENSIONS—

See Figure 3 for dimensions of the PIRVOLHV and

Figure 4 for dimensions of the PointWatch Termination

Box Model PIRTB.

SHIPPING WEIGHT (Approximate)—

Aluminum:

1.9 pounds (0.9 kilogram).

Stainless Steel: 5.0 pounds (2.3 kilograms).

Table 1—Current Loop Output Levels

and Corresponding Status Indications

Figure 1—4 to 20 mA Current Loop Resistance

C1964

18

20

22

24

POWER SUPPLY VOLTAGE (VDC)

26

28

30

32

MAXIMUM LOOP RESISTANCE (OHMS)

400

500

600

700

800

900

LOOP RESISTANCE (OHMS)

Figure 2—PIRVOL Wiring Requirements

A2433

18

20

22

24

POWER SUPPLY VOLTAGE (VDC)

26

28

30

32

MAXIMUM DIST

ANCE FROM POWER SUPPL

Y

T

O PIR

VOLHV IN FEET

16 AWG

14 AWG

12 AWG

18 AWG

500

1000

1500

2000

2500

0

Current Level

Status

23.0 mA

Over 90% by volume

20.0 mA

90% by volume

4.0 mA

Zero gas level (0% by volume)

3.9-2.4 mA

Negative zero drift

2.2 mA

Zero calibration in progress

2.0 mA

Span calibration in progress

1.8 mA

Calibration complete - remove gas

1.6 mA

Calibration fault

1.0 mA

Fouled optics

0.8 mA

24 Vdc line low (less than 17.5 Vdc)

0.6 mA

Calibrate input active at power-up

(probable wiring fault)

0.4 mA

Active channel fault

0.2 mA

Reference channel fault

0.0 mA

CPU system fault, warmup