DETECTOR SEpaRaTION (OpTIONaL)
In applications where the PIRVOLHV must be installed

in a different location from a control device (such as a

transmitter), a PIRTB termination box must be installed at

the PIRVOLHV location to make the electrical connection.

Refer to Figure 11 for a typical separation diagram.

Wiring Requirements for Detector Separation
Shielded four wire cable is recommended for connecting

the PIRTB to the transmitter. Cable with a foil shield is

recommended. The shield of the cable should be open

at the PIRTB and connected to earth ground at the

transmitter termination box. Ensure that the shield wire is

clipped short and insulated with electrical tape to prevent

accidental grounding at the open end.

The maximum distance between the PIRTB and the

transmitter is limited by the resistance of the connecting

wiring, which is a function of the gauge of the wire being

used.

NOTE

It is important to maintain a minimum of +18 volts
dc (including ripple) at the PIRVOLHV. When
determining the appropriate wire size for the
installation, refer to Figure 2. Be sure to take into
account the distance from the power supply to
the PIRVOLHV or to the transmitter and then to the
PIRVOLHV to ensure that the power requirements
are met.

Mounting and Connecting procedure
for Detector Separation
The PIRTB should be mounted to a solid, vibration-free

wall or post. The termination box should be electrically

connected to earth ground.

1. Lubricate the sensor threads with low vapor

pressure silicone grease, then install the sensor in

the conduit entry of the PIRTB. It should be tight to

ensure an explosion-proof installation, however, do

not overtighten.

2. Connect the PIRVOLHV wires to the terminal strip in

the PIRTB.

3. Connect the leadwires from the transmitter to the

appropriate terminals inside the PIRTB. Do not

ground the shield at the PIRTB. Ground the shield at

the transmitter end only.

4. Check the connections inside the PIRTB and place

the cover on the termination box.

5. Mount and wire the transmitter as described in the

instruction manual provided by the manufacturer.

CALIBRATE SWITCH

C2056

HOLD CALIBRATION MAGNET

AT OUTSIDE BASE OF TERMINATION

BOX AT THIS LOCATION

TO ACTIVATE CALIBRATION SWITCH

REMOTE LED

Figure 10—PIRTB Terminals and Calibration Switch

PIRTB

TERMINATION

BOX

SUITABLE WIRING.

MUST MEET ALL LOCAL CODES.

CONTROL DEVICE,

SUCH AS TRANSMITTER

PIRVOL

PROCESS MONITOR

D2030

Figure 11—Detector Separation