Det-Tronics X3302 Multispectrum IR Flame Detector with Pulse Output User Manual

Page 10

Advertising
background image

95-8578

6.1

8

Important

Do not test any wiring connected to the detector
with a meg-ohmmeter. Disconnect wiring at
the detector before checking system wiring for
continuity.

3. Make the final sighting adjustments and use a 14

mm hex wrench to ensure that the mounting arm

assembly is tight.

1
2
3
4
5
6
7
8
9

10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32

+

(A) +290 VDC
B - INPUT 1
B - INPUT 2
B - INPUT 3
B - INPUT 4
B - INPUT 5
B - INPUT 6
B - INPUT 7
B - INPUT 8
D1-1

oi DRIVER

D1-2

oi DRIVER

D1-3

oi DRIVER

D1-4

oi DRIVER

D1-5

oi DRIVER

D1-6

oi DRIVER

D1-7

oi DRIVER

D1-8

oi DRIVER

D2-1

oi DRIVER

D2-2

oi DRIVER

D2-3

oi DRIVER

D2-4

oi DRIVER

D2-5

oi DRIVER

D2-6

oi DRIVER

D2-7

oi DRIVER

D2-8

oi DRIVER

DMA OUT AVAILABLE
DMA OUT
DMA IN
DATA STROBE

33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64

ZONE OUTPUT 1
ZONE OUTPUT 2
ZONE OUTPUT 3
ZONE OUTPUT 4
ZONE OUTPUT 5
ZONE OUTPUT 6
ZONE OUTPUT 7
ZONE OUTPUT 8

FIRE LOGIC “A”

FIRE LOGIC “B”

ALARM OUTPUT

EXTERNAL RESET/INHIBIT

OUTPUTS INHIBITED

FAULT OUTPUT

EXTERNAL ACCEPT

STATUS & DET. OUTPUT S1
STATUS & DET. OUTPUT S2
STATUS & DET. OUTPUT S3
STATUS & DET. OUTPUT S4
STATUS & DET. OUTPUT S5
STATUS & DET. OUTPUT S6
STATUS & DET. OUTPUT S7
STATUS & DET. OUTPUT S8

DATA BUS 0
DATA BUS 1
DATA BUS 2
DATA BUS 3
DATA BUS 4
DATA BUS 5
DATA BUS 6
DATA BUS 7

CHASSIS (EARTH) GND

J1-7

J1-15

J1-5

J1-13

J1-6

J1-14

J1-8

J1-16

J1-9

J1-17

J1-10

J1-18

J1-11

J1-19

J2

R7404 CONTROLLER

J1

10 TO 38 VDC

#2

#1

#19

#22

X3302

DETECTOR 1

#2

#1

#19

#22

#2

#1

#19

#22

X3302

DETECTOR 2

#2

#1

#19

#22

#2

#1

#19

#22

X3302

DETECTOR 3

#2

#1

#19

#22

#2

#1

#19

#22

X3302

DETECTOR 4

#2

#1

#19

#22

#2

#1

#19

#22

X3302

DETECTOR 5

#2

#1

#19

#22

#2

#1

#19

#22

X3302

DETECTOR 6

#2

#1

#19

#22

#2

#1

#19

#22

X3302

DETECTOR 7

#2

#1

#19

#22

#2

#1

#19

#22

X3302

DETECTOR 8

#2
#1
#19

#22

A2266

NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED

TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 µF 400 VDC

NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64.

NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.

NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE

0.5 REQUIREMENTS (SIGNALING LINES A AND C).

24

VDC

+

62

63

64

TO J1-2

0.47 µF / 400 VDC
NON-POLARIZED

GROUND FAULT PROTECTED SYSTEMS

TERMINAL NO.

FUNCTION

1/11

DC– ("C" LEAD)

2/12

DC+ ("A" LEAD)

19

SIGNAL ("B" LEAD)

22

oi

("D" LEAD)

TERMINAL IDENTIFICATION FOR X3302

WITH PULSE OUTPUT.

NOTE: DO NOT CONNECT THE X3302 "A" LEAD (#2/12) TO

TERMINAL J1-3 (290 VDC).

DMA IN AVAILABLE

}

figure 6—a Typical System, X3302 Detectors Wired to R7404 Controller