95-8578

6.1

Detector Wiring

Important

If installing an X3302 in place of an existing
detector, be sure to move the “A” lead (detector
power) at the controller from the +290 Vdc source
to the +24 Vdc source. Do not apply 290 Vdc to
the X3302.

1. Make field connections following local ordinances

and guidelines in this manual.

Figure 4 shows the wiring terminal strip located

inside the detector’s integral junction box.

Figure 5 shows the wiring terminal identification for

the X3302 Flame Detector with pulse output.

Leave the shield open at the detector end and

permanently isolate it from accidental contact with

the case and/or other conductors. At the controller/

fire panel end, connect the shield and power minus

(–) to chassis (earth) ground either directly or

through a 0.47 µF 400 Volt non-polarized capacitor

(not supplied). (Refer to Figures 6 through 10.)

Figures 11 and 12 provide examples of typical

installations with a X3302 wired to a fire alarm

panel.

Figure 13 shows an EOL resistor installed within the

integral wiring compartment of the detector (refer to

“EOL Resistors” for details).

2. Check all field wiring to be sure that the proper

connections have been made.

9

8

7

6

5

4

3

2

1

19

18

17

16

15

14

13

12

11

PULSE OUT

COM FIRE

COM FIRE

N.O. FIRE

N.O. FIRE

N.C. FIRE

N.C. FIRE

COM FAULT

COM FAULT

N.O. FAULT

N.O. FAULT

24 VDC +

24 VDC +

24 VDC –

24 VDC –

24 VDC –

29

28

27

26

25

24

23

22

21

SPARE

SPARE

RS-485 A

RS-485 B

MAN

Oi

B2070

figure 5—X3302 Pulse Wiring Terminal Identification

figure 4—X3302 Terminal Block

figure 3—Q9033 mounting arm without Collar attachment Dimensions in Inches (cm)

(See figure 1 for Correct Detector Orientation .)