Startup procedure – Det-Tronics X3302 Multispectrum IR Flame Detector with Pulse Output User Manual

Page 16

Advertising
background image

95-8578

6.1

14

EOL Resistors
To ensure that the insulating material of the wiring

terminal block will not be affected by the heat generated

by EOL resistors, observe the following guidelines when

installing the resistors.

1. Required EOL resistor power rating must be 5 watts

minimum.

NOTE

EOl resistors must be ceramic, wirewound
type, rated 5 watts minimum, with actual power
dissipation not to exceed 2.5 watts.

this applies

to atEX/IEC installations only.

2. Resistor leads should be cut to a length of

approximately 1 1/2 inches (40 mm).

3. Bend the leads and install the EOL resistor as shown

in Figure 13.

4. Maintain a 3/8 inch (10 mm) minimum gap between

the resistor body and the terminal block or any other

neighboring parts.

NOTE

The EOl resistor can only be used within the
flameproof terminal compartment. Unused
apertures shall be closed with suitable blanking
elements.

STARTuP PROCEDuRE

When installation of the equipment is complete, perform

one or more of the following tests:

• Man

oi

Test — Tests detector output and wiring,

without generating a fire alarm.

• Count Test Mode — Measures actual detector output

to controller (cps), without generating a fire alarm.

• Fire Alarm Test — For complete system test including

detector relays. Generates fire alarm output.

MaNUaL

oi

TEST (Output to Controller)

1. Place the keylock switch in the TEST position.
2. Press the SELECT button to display the desired

zone on the ZONE indicator on the front panel of the

controller.

3. Press and hold the TEST button. The ZONE OUTPUT

LED for the tested zone flashes and the SYSTEM

STATUS display indicates a “6” (fire condition) if the

test is successful.

4. Release the TEST button. The ZONE OUTPUT LED

for the tested zone should remain on steadily.

5. Return to step 2 to test the next detector.

If the system responds differently than indicated above,

proceed with the count test for the problem zone to verify

detector and wiring operation.

COUNT TEST MODE (Output to Controller)
When in the Count Test mode, the frequency of the digital

pulses from the detector is displayed on the ZONE and

DETECTOR indicators on the controller faceplate. The

Count Test mode may be used to check the signal (cps)

from a test fire or false alarm source. This can be useful

during system set-up for sensitivity and time delay

settings. This test is performed in the following manner:

1. Place the keylock switch in the TEST position.
2. Simultaneously press and release the SELECT and

TEST buttons. The Status display will change from

a “1” to an “8” indicating that the controller is in the

Count Test mode of operation.

3. Press the SELECT button until the desired zone is

displayed on the ZONE indicator on the controller

front panel.

figure 13—EOL Resistor Installation

3/8 INCH (10 MM) GAP MINIMUM

11

12

13

14

15

16

17

18

19

B2126

BULKHEAD

Advertising