Det-Tronics X3302 Multispectrum IR Flame Detector with Pulse Output User Manual

Page 25

Advertising
background image

23

95-8578

6.1

FM approval and performance Report – Continued

notE

Refer to the “High Resolution Field of View” charts (page 27) for additional information.

FIELD OF vIEW

very high Sensitivity

Fuel

Size/

Flow Rate

Distance

feet (m)

horizontal

(degrees)

avg. horiz.

Response Time

(seconds)

vertical

(degrees)

avg. vert.

Response Time

(seconds)

Hydrogen

30 inch plume/

100 SLPM*

100 (30.5)

+45

-45

2

2.5

+45

-30

8

1.5

Methanol

1 x 1 foot

70 (21.3)

+45

-45

10

6

+45

-30

8.5

6

* Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).

high Sensitivity

Fuel

Size/

Flow Rate

Distance

feet (m)

horizontal

(degrees)

avg. horiz.

Response Time

(seconds)

vertical

(degrees)

avg. vert.

Response Time

(seconds)

Hydrogen

30 inch plume/

100 SLPM*

75 (22.9)

+45

-45

4

2.5

+45

-30

3

3

Methanol

1 x 1 foot

52.5 (16.0)

+45

-45

4.5

3.5

+45

-30

4.5

2.5

* Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).

Medium Sensitivity

Fuel

Size/

Flow Rate

Distance

feet (m)

horizontal

(degrees)

avg. horiz.

Response Time

(seconds)

vertical

(degrees)

avg. vert.

Response Time

(seconds)

Hydrogen

30 inch plume/

100 SLPM*

50 (15.2)

+45

-45

4.5

3.5

+45

-30

3

5

Methanol

1 x 1 foot

35 (10.7)

+45

-45

9.5

6

+45

-30

10.5

5.5

* Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).

Low Sensitivity

Fuel

Size/

Flow Rate

Distance

feet (m)

horizontal

(degrees)

avg. horiz.

Response Time

(seconds)

vertical

(degrees)

avg. vert.

Response Time

(seconds)

Hydrogen

30 inch plume/

100 SLPM*

25 (7.6)

+45

-45

2

2.5

+45

-30

2.4

2

Methanol

1 x 1 foot

17.5 (5.3)

+45

-45

7

8.5

+45

-30

5.5

6

* Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).

Advertising