FM approval and performance Report – Continued

RESpONSE ChaRaCTERISTICS

very high Sensitivity

Fuel

Size/Flow Rate

Distance

feet (m)

average Response

Time (seconds)

Hydrogen

30 inch plume/100 SLPM*

100 (30.5)

3

Methanol

1 x 1 foot

70 (21.3)

5

* Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).

high Sensitivity

Fuel

Size/Flow Rate

Distance

feet (m)

average Response

Time (seconds)

Hydrogen

30 inch plume/100 SLPM*

75 (22.9)

3

Methanol

1 x 1 foot

52.5 (16.0)

2

* Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).

Medium Sensitivity

Fuel

Size/Flow Rate

Distance

feet (m)

average Response

Time (seconds)

Hydrogen

30 inch plume/100 SLPM*

50 (15.2)

4

Methanol

1 x 1 foot

35 (10.7)

4

* Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).

Low Sensitivity

Fuel

Size/Flow Rate

Distance

feet (m)

average Response

Time (seconds)

Hydrogen

30 inch plume / 100 SLPM*

25 (7.6)

3

Methanol

1 x 1 foot

17.5 (5.3)

3

* Standard Liters Per Minute (Standard conditions defined as +25°C and 14.696 PSIA).