1.1

10

stAtus inFo menu
This menu (read only) shows extensive status information about the detector.

1) warmup (Y/n)

Device is in the power-up time delay (warm-up) mode.

2) Fire (Y/n)

Indicates “Y” if the device is in a fire alarm status — analog output is at 20 mA, fire

alarm relay is actuated and LED is red.

3) uv Alarm (Y/n)

Indicates "Y" if the UV detector is signaling an alarm.

4) uv Pre Alarm (Y/n)

Indicates "Y" if the UV detector is in a pre-alarm state.

5) Auto uv oi Fault (Y/n)

Automatic UV Oi Fault. Check UV viewing window and Oi reflector plate cleanliness.

6) manual oi at start

Manual Oi at Start. On power-up a manual Oi was started. Check the external input

wiring.

7) snsr hdwr Fault (Y/n)

Sensor hardware fault.

8) hiB hdwr Fault (Y/n)

HART Interface Board hardware fault.

9) int comm Fault (Y/n)

Internal communication fault.

10) incompatible Fault (Y/n)

Sensor module firmware version is not compatible with HART Interface Board.

11) voltage Fault (Y/n)

Detector operating voltage is out of tolerance.

12) hardware menu

Refer to sub-menu.

13) oi menu

Refer to sub-menu.

Device Info Menu

1) General Info Menu
2) HART Info Menu
3) Status Info Menu
4) Detector Settings
5) History Menu

X2200 Root Menu

1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu

Status Info Menu

1) Warmup (Y/N)
2) Fire (Y/N)
3) UV Alarm (Y/N)
4) UV Pre Alarm (Y/N)
5) Auto UV Oi Fault (Y/N)
6) Manual Oi at Start
7) Snsr Hdwr Fault (Y/N)
8) HIB Hdwr Fault (Y/N)
9) Int Comm Fault (Y/N)
10) Incompatible Fault (Y/N)
11) Voltage Fault (Y/N)
12) Hardware Menu
13) Oi Menu