detector settings
This menu shows factory settings relating to relay operation, detector sensitivity and response.

1) uv mode

UV Mode: Standard or Arc.

2) Arc rejection

Detector ARC Rejection setting: Low, Medium, High, or Very High.

3) uv sensitivity

Detector UV sensitivity setting: Low, Medium, High, or Very High.

4) Auto oi enabled

Auto Oi Enabled. If (Y) an Oi test will be conducted periodically without manual

input.

5) Fire relay (nL/L)

Fire Relay: Latching (L) or Non-Latching (NL).

6) Fault relay (nL/L)

Fault Relay: Latching (L) or Non-Latching (NL).

7) Aux relay (nL/L)

Aux Relay: Latching (L) or Non-Latching (NL).

8) heater disabled

Heater Disabled. If (Y) the optics heater is not enabled to prevent condensation and

icing.

9) Aux Function

Aux function: Pre Alarm or UV Alarm.

10) Aux relay (ne/nde)

Aux Relay: Normally Energized (NE) or Normally De-Energized (NDE).

Device Info Menu

1) General Info Menu
2) HART Info Menu
3) Status Info Menu
4) Detector Settings
5) History Menu

X2200 Root Menu

1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu

Detector Settings

1) UV Mode
2) ARC Rejection
3) UV Sensitivity
4) Auto Oi Enabled
5) Fire Relay (NL/L)
6) Fault Relay (NL/L)
7) Aux Relay (NL/L)
8) Heater Disabled
9) Aux Function
10) Aux Relay (NE/NDE)