1.1

11

hArdwAre menu

1) temperature

Actual integral temperature of detector (in degrees Celsius).

2) temp range Fault

Detector integral temperature out of range —

Operating range: –40°C to +75°C (–40°F to +167°F).

3) voltage

Actual detector supply voltage (must be 18 to 30 Vdc).

4) volt Fault

Supply voltage is out of range. Operating voltage must be 18 to 30 Vdc.

5) manual oi at start

Manual Oi at Start. On power-up a manual Oi was started. Check the external input wiring.

oi menu

1) consecutive uv oi Fails

Allowable number of consecutive UV Oi failures to produce a fault. Factory set to 3

(minutes). This is the time between fault occurrence and annunciation.

2) oi calibrate Active

Oi calibration is in progress.

3) uv oi cal Fault

UV Oi calibration has detected a fault condition.

4) manual oi Active

A manual Oi test is in progress.

5) manual uv oi Fault

Manual UV Oi fault. Check UV viewing window and Oi reflector plate cleanliness.

Hardware Menu

1) Temperature
2) Temp Range Fault
3) Voltage
4) Voltage Fault
5) Manual Oi at Start

Device Info Menu

1) General Info Menu
2) HART Info Menu
3) Status Info Menu
4) Detector Settings
5) History Menu

X2200 Root Menu

1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu

Status Info Menu

1) Warmup (Y/N)
2) Fire (Y/N)
3) UV Alarm (Y/N)
4) UV Pre Alarm (Y/N)
5) Auto UV Oi Fault (Y/N)
6) Manual Oi at Start
7) Snsr Hdwr Fault (Y/N)
8) HIB Hdwr Fault (Y/N)
9) Int Comm Fault (Y/N)
10) Incompatible Fault (Y/N)
11) Voltage Fault (Y/N)
12) Hardware Menu
13) Oi Menu

Device Info Menu

1) General Info Menu
2) HART Info Menu
3) Status Info Menu
4) Detector Settings
5) History Menu

X2200 Root Menu

1) Fire (Yes/No)
2) Fault (Yes/No)
3) Device Info Menu
4) Command Menu
5) Device Setup Menu

Oi Menu

1) Consecutive UV Oi Fails
2) Oi Calibrate Active
3) UV Oi Cal Fault
4) Manual Oi Active
5) Manual UV Oi Fault

Status Info Menu

1) Warmup (Y/N)
2) Fire (Y/N)
3) UV Alarm (Y/N)
4) UV Pre Alarm (Y/N)
5) Auto UV Oi Fault (Y/N)
6) Manual Oi at Start
7) Snsr Hdwr Fault (Y/N)
8) HIB Hdwr Fault (Y/N)
9) Int Comm Fault (Y/N)
10) Incompatible Fault (Y/N)
11) Voltage Fault (Y/N)
12) Hardware Menu
13) Oi Menu