4.2

95-8654

2

theory oF operation

During normal operation, the ASH Module continuously

checks the loop for alarm and fault conditions and

executes user defined programmed logic that coordinates

the control of the field devices. The ASH Module reports

any device based fault and alarm conditions to the EQP

Controller.

The ASH Module can support different Apollo Discovery

and XP95 devices (see Table 3). The supported devices

include smoke detectors, heat detectors, manual calls,

sounders, beacons and I/O modules. The addressable

devices are configured individually via the ASH Apollo

Editor in the S

3

software.

To ensure reliable system operation, the ASH Module can

continuously monitor its input and output circuits for open

and short circuit conditions. The EQP Controller also

continuously monitors the status of the ASH Module as

well as the status of each device connected to the ASH

Module.

The controller communicates with the ASH Module by

continuously broadcasting a heartbeat signal over the

LON (Figure 1). This heartbeat is used for verifying

the integrity of the LON and for keeping the addressed

field devices from going into a fault isolation mode.

The heartbeat also contains the current date and time,

which is used by the field devices to log status events

and calibrations. For detailed information on the EQP

Controller, refer to instruction manual 95-8533.

ISOLATORS
Isolators are used to disconnect a shorted section

of the ASH Module Apollo loop so that the remaining

sections can continue to operate. In accordance

with the NFPA 72 standard for SLCs, the ASH Module

supports Class A, Class B, and Class X SLC wiring

styles.

Note

A maximum of six isolators may be used on the
Apollo loop.

For the Class A wiring style, isolators are optional on the

ASH Module Apollo loop where only a single zone is

monitored. During a single open, a single ground fault,

or the combination of a single open and a single ground

fault, the Class A pathway shall maintain alarm receipt

capabilities. See Figure 2 for Class A pathway.

Class B requires that a spur configuration be used, with

the single spur connected to the “Loop Out” terminals on

the ASH Module. The Class B pathway is intended for

use in a single zone system. When a single ground fault

is present, alarm receipt capabilities shall be maintained.

Devices beyond a single open will lose connection, but

all devices will lose connection for a short. See Figure 3

for Class B pathway.

C2532

NODE 1

NODE 8

HARDWIRED LON CONNECTION

NODE 3

NODE 6

NODE 2

NODE 7

ASH MODULE

NODE 5

NODE 4

EQP

CONTROLLER

EAGLE QUANTUM PREMIER
Safety System Controller

Fire Alarm

Inhibit

Power

Supr

High Gas

Trouble

Cntrl Flt

Lon Fault

Low Gas

Ack

Silence

Out Inhibit

Eagle Quantum Premier

Time & Date

Cancel

Enter

Next

Previous

Reset

Acknowledge Silence

DET-TRONICS

®

NODE 64

NODE 1

...

NODE 63

NODE 3...

NODE 2

. . . . . . . . . . . . .

.......

........

ASH MODULE APOLLO LOOP

2-WAY COMMUNICATION

. . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . .

A2589

ASH MODULE

NODE 64

NODE 1

...

NODE 63

NODE 3...

NODE 2

SINGLE

ZONE

. . . . . . . . . . . . .

. . . . . . . . . . . . . . . . .

.......

........

ASH MODULE APOLLO LOOP

2-WAY COMMUNICATION

. . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . .

ISOLATOR

(Optional)

ISOLATOR

(Optional)

ISOLATOR

(Optional)

ISOLATOR

(Optional)

ENCLOSURE

Figure 1—EQP LON with ASH Module Communication

Figure 2—Class A Pathway (isolators are optional)

A2590

ASH MODULE

NODE 64

NODE 2...

...NODE 63

NODE 1

SINGLE

ZONE

. . . . . . . . . . . . .

. . . . . . . . . . . . .

ASH MODULE APOLLO LOOP

2-WAY COMMUNICATION

. . . . . . . .

. . . . . . . .

. . . . . . . .

ENCLOSURE

Figure 3—Class B Pathway (without isolators)